0 <br />S W RCB, January 2002 <br />• Page _ of <br />7. UNDER -DISPENSER CONTAINMENT (UDQ TESTING <br />Test Method Developed By: 0 UDC Manufacturer 0 Industry Standard X Professional Engineer <br />D Other (Spec) <br />Test Method Used: D Pressure 0 Vacuum X Hydrostatic <br />0 Other (Specie) <br />Test Equipment Used: Caldwell Level Change Indicator <br />UDC # 9&10 -RT UDC # 1&2 -CL <br />UDC Manufacturer: Bravo Bravo <br />Equipment Resolution: .002 <br />UDC # 3&4 -CL <br />Bravo <br />UDC # 5&6 -CL <br />Bravo <br />UDC Material: <br />Coated Steel <br />Coated Steel <br />Coated Steel <br />Coated Steel <br />UDC Depth: <br />10" <br />9" <br />9" <br />9" <br />Height from UDC Bottom to Top <br />of Highest Piping Penetration: <br />See Comments <br />See Comments <br />See Comments <br />See Comments <br />Height from UDC Bottom to <br />Lowest Electrical Penetration: <br />See Comments <br />See Comments <br />See Comments <br />See Comments <br />Condition of UDC prior to <br />testing: <br />Dry <br />Dr; <br />Dry <br />Dry <br />Portion of UDC Tested <br />Water Level 8" <br />Water Level 7" <br />Water Level 7" <br />Water Level 7" <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />product and water)?* <br />Yes XNo DNA <br />Yes XNo DNA <br />Yes XNo DNA <br />Yes XNo DNA <br />Turbine shutdown response time <br />N/A <br />N/A <br />N/A <br />N/A <br />Is system programmed for fail- <br />safe shutdown?* <br />X Yes 0 No 0 NA <br />X Yes ONO DNA <br />X Yes ONO DNA <br />X Yes ONO DNA <br />Was fail-safe verified to be <br />operational?* <br />❑Yes XNo 0 N <br />OYes XNo DNA <br />❑Yes XNo DNA <br />❑Yes XNo DNA <br />Wait time between applying <br />water and starting test <br />5 Minutes <br />5 Minutes <br />5 Minutes <br />5 Minutes <br />Test Start Time: <br />11:55 <br />10:00 <br />10:05 <br />10:10 <br />Initial Reading Rr): <br />.001 <br />.001 <br />.001 <br />.001 <br />Test End Time: <br />12:25 <br />10:30 <br />10:35 <br />10:40 <br />Final Reading (RF): <br />.001 <br />.001 <br />.001 <br />.001 <br />Test Duration: <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />Change in Reading RF-Rr: <br />0 <br />0 <br />0 <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005/30 Minutes <br />.005/30 Minutes <br />.005/30 Minutes <br />.005/30 Minutes <br />st` <br />sa.' <br />, <br />p <br />'pailTeifl <br />Was sensor removed for testing? <br />X Yes 0 No 0 NA <br />X Yes 0 No 0 NA <br />X Yes ONO DNA <br />X Yes ONO DNA <br />Was sensor properly replaced and <br />verified functional after testing? <br />X Yes 0 No 0 NA <br />X Yes ONO DNA <br />X Yes ONO DNA <br />X Yes ONO DNA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />All Penetrations enter from of Bravo System UDC's. <br />RT=Retail Island/CL=Card Lock Island <br />If the entire depth of the UDC is not tested, specify how much was tested. If the answer to Ally of the questions indicated with an <br />rterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />