Laserfiche WebLink
Page 3 of 7 <br /> 5. SECONDARY PIPE TESTING <br /> Test Method Developed By: Piping Manufacturer Industry Standard X Professional Engineer <br /> Other(Specify) <br /> Test Method Used: X Pressure Vacuum Hydrostatic <br /> Other(Spect&) <br /> Test Equipment Used: Compressor Equipment Resolution: <br /> Piping Run# 1 Piping Run# 2 Piping Run# Piping Run# <br /> Piping Material: Fiberglass Fiberglass <br /> Piping Manufacturer: Smith Fiberglass Smith Fiberglass <br /> Piping Diameter: 2" 2" <br /> Length of Piping Ron: 55' 50' <br /> Product Stored: Unleaded Diesel <br /> Method and location of From Soup to Dispenser From Sump to Dispenser <br /> i in -mn isolation: <br /> Wait time between applying <br /> pressure/vacuum/water and <br /> starting test: Not Testable 30 Min <br /> Test Start Time: 10:00 <br /> Initial Reading(Rr): 5 psi <br /> Test End Time: 11:00 <br /> Final Reading(Rr): 5 psi <br /> Test Duration: I Hr <br /> Change in Reading(R,-RI): 0 <br /> Pass/Fail Threshold or <br /> Criteria I psi Loss 1 psi Loss I psi Loss I psi Loss <br /> : <br /> Test Result: I ❑ Pass ❑✓ Fail ❑✓ Pass❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail <br /> Comments—(include information on repairs madeprior to testing and recommended ollow-upforfailed tests) <br /> Secondary pipe test on#1 (SPT#1) untestable,Test boots are on.Not holding pressure. Not enough room <br /> to make repairs.Dispenser needs to be removed in order to make repairs. <br /> Recommendation: Needs new test boots installed and retested. <br />