• • RECEIVED <br /> JAN 0 3 2017 <br /> 7. UNDER-DISPENSER CONTAINMENT(UDC)TESTING <br /> Test Method Developed By: ❑ UDC Manufacturer ®Industry Standard ®Nkdit#(s3N91'I€dpfA <br /> ❑ Other(Specrfy) DEPARTMENT <br /> Test Method Used: ❑Pressure ❑ Vacuum ®Hydrostatic <br /> ❑ Other(Specify) <br /> 11 Test Equipment Used: Incou Sump Tester Equipment Resolution: +/-0.002" <br /> UDC#1/2 UDC#3/4 UDC#5/6 UDC#7/8 <br /> UDC Manufacturer: Environ Environ Environ Environ <br /> UDC Material: Green Plastic Green Plastic Green Plastic Green Plastic <br /> UDC Depth: 31" 31" 31" 31" <br /> Height from UDC Bottom to Top ?" 7" 7" 7" <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 4" 4" 4" 4" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to <br /> testing: Good Good Good Good <br /> Portion of UDC Tested 2"above piping 2"above piping 2"above piping 2"above piping <br /> Does turbine shut down when <br /> UDC sensor detects jliquid(both ❑Yes❑No M NA ❑Yes❑ No ®NA ❑Yes❑No ®NA ❑Yes❑No RNA <br /> product and water)? <br /> Turbine shutdown re once time N/A N/A N/A N/A <br /> Is system programmed for fail- <br /> safe shutdown?' ❑yes 11No ®NA ❑Yes❑No ®NA ❑Yes❑No RNA E3Yes❑No ®NA <br /> Was fail-safe verified to be <br /> operational?' 11Yes❑No ®NA ❑Yes❑No RNA ❑Yes❑No RNA ❑Yes[INo ®NA <br /> Wait time between applying <br /> pressure/vacuum/water and 30 minutes 30 minutes 30 minutes 30 minutes <br /> starting test <br /> Test Start Time: _ 10:53 am <br /> Initial Reading(R& 6.5150 <br /> Test End Time: 11:08 am <br /> Final Reading(RF): 6.5149 <br /> Test Duration: 15 min. <br /> Change in Reading(RF-Ri): 0.0001 <br /> Pass/Fail Threshold or Criteria: +/_0.002" +/-0.002" +/_0.002" +/-0.002" <br /> Test Result: ❑ Pass <br /> ❑ I@ Fail ❑ Pass ® Fail 11 Pass ®Fall ® Pass [j Fail <br /> Was sensor removed for testing? Yes®No❑NA ❑Yes®No❑NA ❑Yes®No❑NA ®Yes❑No❑NA <br /> Was sensor properly replaced and ❑yes[INo[3NA ❑Yes❑No C1NA ❑Yes❑No E]NA ®Yes❑No❑NA <br /> verified functional after testin 7 <br /> Comments—(include information on repairs made p•ior to testing, and reconmtended follow-up fur failed tests) <br /> "Sensor functionality was not confirmed.This procedure is not part of the Secondary Containment testing scope of work". <br /> Visual failures to UDC's 1/2, 3/4, &5/6 jumper lines. <br /> If the entire depth of the UDC is not tested,specify how much was tested. If the answer to Any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />