• • RECEIVED <br /> JAN 0 3 2017 <br /> 7. UNDER-DISPENSER CONTAINMENT(UDC)TESTING <br /> Test Method Developed By: ❑ UDC Manufacturer N Industry Standard ❑ FEAVIRO LTH <br /> ❑ Other(Spectfy) DEPARTMENT <br /> Test Method Used: ❑ Pressure ❑ Vacuum ®Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used: Incon Sump Tester Equipment Resolution: +/-0.002" <br /> UDC_#9/10 UDC#11/12 <br /> UDC Manufacturer: Environ Environ <br /> UDC Material: Plastic Plastic <br /> UDC Depth: 31" 31" <br /> Height from UDC Bottom to Top 7„ 7„ <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 4" 4" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Good Good <br /> testing: <br /> Portion of UDC Tested 2"above piping 2"above piping <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ❑Yes❑No ®NA ❑Yes❑No ®NA <br /> product and water)? <br /> ater?� <br /> Turbine shutdown response time N/A N/A <br /> Is system programmed for fail- <br /> safe shutdown? ❑yea❑No ®NA ❑Yas❑No ®NA <br /> Was fail-safe verified to be <br /> operational?' ❑Yea❑No ®NA [__IYes[INo ®NA <br /> Wait time between applying <br /> pressure/vacuum/water and 30 minutes 30 minutes <br /> starting test <br /> Test Start Time: 2:07 pra <br /> Initial Reading(R,): 2.8474 <br /> Test End Time: 2:22 pm <br /> Final Reading(RP): 2.8487 <br /> Test Duration: 15 min. <br /> Change in Reading(RF-R,): 0.0013 <br /> Pass/Fail Threshold or Criteria: +/-0.002" <br /> Test Result: ® Pass ❑Fail ❑ Paas ®Fall <br /> Was sensor removed for testing? ®Yes❑No❑NA ❑Yes® No❑NA <br /> Was sensor properly replaced and ®yes❑No❑NA ❑Yes❑No❑NA <br /> verified functional after testin T <br /> _Comments—(include information on repairs made prior to testing and recommended follow-up for ailed tests) <br /> "Sensor functionality was not confirmed.This procedure is not part of the Secondary Containment testing scope of work". <br /> Visual failures to UDC 11/12. <br /> If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />