JUN-Cb-.OUY 1b:UY Service Station Systems 408 938 8888 P.09 <br />*45W <br />10. SPILL/OVF.RFTT.T. rQNTAYKMTi W1r RnYre <br />Facility is Not Equipped With Spill/Overfill Containment Boxes p <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑ Spill Bucket Manufacturer 14 industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure 0 Vacuum IR Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Incon Sump Tester <br />Fill Spill Box 0 87 Fill Spill Box # 89 <br />Equipment Resolution: +/-0.002" <br />Fill Spill Box # 91 FBI Spill Box # Diesel <br />Bucket Diameter: <br />l0" <br />10" <br />10" 10" <br />Bucket Depth: <br />12" <br />12" <br />12" 12" <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 min. <br />10 min. <br />10 min. 10 min. <br />Test Start Time: <br />7:15 am <br />7:36 am <br />7:36 am 7:15 am <br />Initial Reading <br />3.8106 <br />1.6341 <br />4.2184 2.6074 <br />Test End Time: <br />7:31 am <br />7:52 am <br />7:52 am 7:31 am <br />Final Reading (RF); <br />3.8105 <br />1.6341 <br />4.2186 2.6071 <br />Test Duration: <br />16 min. <br />16 min. <br />16 min. 16 min. <br />Change in Reading (RFR): <br />-0.0001 <br />None <br />+0.0002 -0.0003 <br />Pass/Fail Threshold or <br />Criteria: <br />+/-0.002" <br />+/-0.002" <br />+/-0.002" +/-0.002" <br />Test Result: <br />® Pass Fail <br />® Pass Fail <br />0 Pass Fail ® Pass Fail <br />Comments — (include information on repairs made prior to testing and recommended follow-vp for jailed tests) <br />