Laserfiche WebLink
TS7393-05 • Page_3_of—4- <br /> 5. SECONDARY PIPE TESTING <br /> Test Method Developed By: ❑ Piping Manufacturer ®Industry Standard ❑Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used: ® Pressure ❑ Vacuum ❑Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: ANALOG DIAL GAUGE Equipment Resolution: <br /> Piping Run# Piping Run# Piping Run# Piping Run# <br /> SUPPLY <br /> Piping Material: FIBERGLASS <br /> Piping Manufacturer: A.O. SMITH <br /> Piping Diameter: 6 INCH <br /> Length of Piping Run: APPROX. 30 FEET <br /> Product Stored: RECLAIM FLUID <br /> Method and location of TEST BOOTS <br /> piping-nm isolation: <br /> Wait time between applying <br /> pressure/vacuum/water and 15 MIN <br /> starting test: <br /> Test Start Time: 9:00 AM <br /> Initial Reading(Ril: 5 PSI <br /> Test End Time: 10:00 AM <br /> Final Reading(RF): 2 PSI <br /> Test Duration: 1 HOUR <br /> Change in Reading(RF-Ril: 3 PSI <br /> Pass/Fail Threshold or 0 PSI <br /> Criteria: <br /> Test Result: ❑ Pass OF" ❑ Pass ❑ Fail ❑ Pass ❑Fail ❑ Pass ❑ Fail <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for farted tests) <br /> SECONDARY PIPING FAILED DUE TO A BAD BLUE LINE TEST BOOT LOCATED IN THE PIPING <br /> SUMP LOCATED ON THE TANK PAD. AFTER SPENDING APPROXIMATELY 1 HOUR MAKING <br /> ADJUSTMENTS TO THE TEST BOOTS AND CLAMPS, IT WAS STILL UNABLE TO HOLD A <br /> CONSTANT 5 PSI ON PIPING. BOOT WILL NEED TO BE REPLACED ALONG WITH MAKING <br /> CORRECTIONS TO THE SECONDARY PIPING(REMOVAL OF SMITH GLUE) IN ORDER FOR TEST <br /> TO BE PERFORMED. <br /> * TEST PORTS ARE LOCATED IN TRANSITION SUMP. <br />