My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2016 - 2018
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
G
>
GRANT LINE
>
3250
>
2300 - Underground Storage Tank Program
>
PR0518288
>
COMPLIANCE INFO_2016 - 2018
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
8/28/2023 9:08:35 AM
Creation date
11/8/2018 10:21:53 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2016 - 2018
RECORD_ID
PR0518288
PE
2361
FACILITY_ID
FA0013810
FACILITY_NAME
COSTCO WHOLESALE #658
STREET_NUMBER
3250
Direction
W
STREET_NAME
GRANT LINE
STREET_TYPE
RD
City
TRACY
Zip
95377
CURRENT_STATUS
01
SITE_LOCATION
3250 W GRANT LINE RD
P_LOCATION
03
QC Status
Approved
Scanner
WNg
Supplemental fields
FilePath
\MIGRATIONS3\G\GRANT LINE\3250\PR0518288\COMPLIANCE INFO 2016 - PRESENT.pdf
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
416
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
6. PIPING SUMP TESTING <br /> Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard p Professional Engineer <br /> ❑ Other tS'pegf <br /> Test Metliod Used: ❑Pressure. ❑ Vacuum E Hydrostatic <br /> ❑ Other{Specify) <br /> Test Equipment Used: Incon TS-STS Sump Test System Equipment Resolutiow +1-0.002" <br /> T1 -87 T2-87 T3-91 W <br /> Sump Diameter: 48" 4811 48" <br /> Sump Depth: 54" 54" 61" <br /> Sump Material: Fiber lass Fiberglass Fiberglass <br /> Height from'Tank Top to Top of 29„ 20" 14" <br /> Highest Piping Penetration; <br /> Height from.Tank Top to Lowest 22" 22" 16" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Good Good Good <br /> Portion of Sump Tested' 4" Above Pen, 4" Above Pen. 4"Above Pen. <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ❑ Yes❑No ENA ❑Yes ❑No ®NA. ❑ Yes❑No E.NA ❑Yes©No E NA <br /> product and mater)?` <br /> Turbine shutdown response time N/A N/A N/A <br /> Is system progrannned for foil-safe ❑ Yes❑No. ENA ❑ Yes❑No ENA ❑ Yes❑ No E NA ❑Yes ❑ No ENA <br /> shutdown? <br /> Was fail-safe verified to be ❑Yes❑No Z NA ❑ Yes❑No ENA ❑Yes❑No:E.NA ❑ Yes❑No E NA <br /> operational?' <br /> Wait time between applying <br /> pressure/vacuunrlwater and starting 30 minutes 30 minutes 30 minutes <br /> test: <br /> Test Start Time: 06:37 AM 07:14 AM 07:44 AM <br /> Initial Reading(Rt): 4.9628 5.8926 5,7839 <br /> Test End Time: 06:52 AM 07:29 AM 07:59 AM <br /> Final Reading.(RF): 4,9625 5.892 5.7832 <br /> Test Duration: 15 min. 15 min. 15 min. <br /> Change in Reading(RF-]RI): -0,0003 -0.0006 -0.0007 <br /> Pass/Fail Threshold or Criteria: +1-0.00211 +1-0.002 +/-0.002 <br /> Test Result: Pass Pass Pass <br /> Was sensor removed:for testing? Yes Yes Yes <br /> Was sensor properly replaced and Yes Yes Yes <br /> verified functional after testing? <br /> _Comments= (h7clude.h7formallon7on repairs trade prior to testing, and reconttt)en.ded follotiv-up for,failed tests) <br /> Sensor functionality was not confirmed. This procedure is not nart of the Secondary Containment Testing scone of work, <br /> 6 20 <br /> EPW1nrtuMFN1AL HEALTH <br /> PERMITISERVICES <br /> I If the endre-depfh of the sinnp.is not tested,specify how irtuch was tested. If the answer.to M of the questions indicated with an <br /> asierisk(*)is"NO"or"NA",the entire sump must be tested. (See.SWRCB LG-16.Q) <br />
The URL can be used to link to this page
Your browser does not support the video tag.