Laserfiche WebLink
0 GILBARC <br /> PROBE INSTALLATION INSTRUCTION �lObCirCvi <br /> €: / <br /> I LOAF <br /> It, <br /> >,� T <br /> aD.INPO OR <br /> RING <br /> AT <br /> Figure 4. Magnetostrictive Probe Installation Kit with 4" Floats. <br /> Figure 7. 3" Probe Riser Adaptor Ring Installation <br /> /t\ D. FLOAT ASSEMBLIES <br /> \'\• <br /> IMPORTANT! <br /> � When installing high alcohol magnetostriMiveprobe, <br /> �igure 5. Magnetostrictive Probe Installation Kit with 2" Floats. Form No. PA0300XXXXXXX note the following: <br /> The Magnetostrictive Probe Installation Kit for use <br /> with high alcohol probes,Form No.Q13161-XXX does <br /> yy not contain a water float Adding a water float or <br /> sinker in this application will cause equipment to <br /> malfunction. A float kit containing only a fuel float <br /> must be used with this probe. <br /> s <br /> 1. Remove the fuel Float and water Boat from the Magneto- <br /> strictive Probe Installation Kit box (refer to Figure 4 or 5). <br /> \ 2. Ballast rings are factory-installed on the water float of <br /> magnetostrictive probes to ensure proper float action. The <br /> f\ A�APiOR ring type varies with the Fluid being measured. Float ballast <br /> RING rings are available for the following liquids: <br /> GNISTEP <br /> Ballast Ring G2 — used with: aviation gas, regular <br /> unleaded gasoline, premium unleaded gasoline, leaded <br /> gasoline,gasohol. <br /> Ballast Ring L2— used with: motor oil,toluene,gear oil <br /> 90W, transmission fluid, used oil. <br /> Figure 6. 4" Probe Riser Adaptor Ring Installation Ballast Ring D2 — used with: jet fuel, kerosene, diesel <br /> #2. <br /> The following liquids require only the water float mounting <br /> tube (see Figure 10), since water is not measurable in the <br /> liquid: ethylene glycol (antifreeze), propylene glycol (anti- <br /> freeze),wastewater,windshield washer fluid,fuel oil#4 with <br /> specific gravity greater than 0.925. <br /> 3 <br />