REGE <br /> SEN 17 2015 <br /> SWRCB,January 2002 ENV1R®N�A A'�-p <br /> 6. PIPING SUMP TESTING Ion' 'A l 1t1l�age o <br /> Test Method Developed By: ❑Sump Manufacturer ❑Industry Standard RProfessional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum gHydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: I NCON TS—STS Equipment Resolution:0.0 0 01 " <br /> Sump#87Syphon Sump487Maste Sump# 87Slave Sump# 91 <br /> Sump Diameter: 5211 5211 52" 5211 <br /> Sump Depth: 57" 57" 58" 57" <br /> Sump Material: FRP FRP FRP FRP <br /> Height from Tank Top to Top of 1 sit 27" 22" 2511 <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 3611 3811 3211 3 2" <br /> Electrical Penetration: _ <br /> Condition of sump prior to testing: Clean Clean Clean Clean <br /> Portion of Sump Testcd' 3811 4011 3411 32" <br /> Does turbine shut down when :91 Yes ❑No ❑NA <br /> sump sensor detects liquid(both 9Yes Ll No DNA XYes ❑No DNA NYes ❑No DNA <br /> product and water)?* <br /> Turbine shutdown response time 4 s e c 3 s e c 3 s e c 5 s e c <br /> Is system programmed for fail-safe M Yes ❑No ❑NA PSYes ❑No ❑NA ;XYes ❑No ❑NA NYes ❑No ❑NA <br /> shutdown?* <br /> Was fail-safe verified to be VYes ❑No 11 NA MYes 0 N ❑NA [XYes. ❑No DNA ZYes ONO DNA <br /> operational?` <br /> Wait time between applying <br /> pressure/vacuum/water and starting l O m i n 1 0 m i n l O m i n O m i n <br /> test: <br /> Test Start Time: 10 :43a10 :43am 11 :45am 11 :45am <br /> Initial Reading(R{): 4 .3425" 5.6689" 2. 3401 " 3 .7490" <br /> Test End Time: 10 : 58am 10 : 58am 12:00pm 12:00pm <br /> Final Reading(RF): 4.3417" 5.6688" 2.3398" 3 .7491 <br /> " <br /> 'rest Duration: 1 5min 1 5min 1 5min 1 5min <br /> Change in Reading l+tF-Rj): 0 .0 0 0 8" 0.000111 0.0003" 0 .0 0 0 1 1, <br /> Pass/Fail Threshold or Criteria: ±O .002" ±0.002" ±0 .002" ±0 .002" <br /> Test Result: N Pass ❑Fail r' Pass ❑Fail k Pass ❑Fail X1 Pass ❑Fail <br /> f <br /> Was sensor removed for testing? _VYes ❑No ❑NA 2 Yes ❑No ❑NA 1,RYes ❑No ❑NA XYes ❑No ❑NA <br /> Was sensor properly replaced and K Yes ❑No ❑NA xYes 0 No 7 N BYes ❑No DNA XYes LINO DNA <br /> verified functional after testing? <br /> Comments (include information on repairs made prior to testing and recommended jollrnv-up forjarled tests) <br /> If the entire depth of the sump is not tested,specily how much was tested. If the answer to Wy of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />