NOTES: <br /> 1. FLEXIBLE RUBBER TUBE MUST BE ATTACHED TO EXTRACTION VALVE CLIP. MINI CHECK VALVE- <br /> SEE NOTE#5. <br /> 2. CONTROLLER MUST BE INSTALLED IN AN ACCESSIBLE LOCATION. <br /> EXTRACTION VALVE- <br /> 3.APPROPRIATE PIPE BRACING MUST BE 12"(305mm)AWAY FROM EXTRACTION VALVE ON BOTH SIDES TO ALLOW COUPLINGS TO SLIDE FREELY. SEE NOTE#3 AND#4 <br /> 4.TOP OF EXTRACTION VALVE MUST BE INSTALLED EVEN WITH TOP OF CASE AND CLEARANCE MUST BE PROVIDED TO ALLOW FOR UNOBSTRUCTED MOVEMENT. 1/4"I.D. FLEXIBLE RUBBER TUBE <br /> FLEXIBLE RUBBER <br /> INSTALLATION NOTES FOR VACUUM DRAINAGE PIPING. 5. MINI CHECK VALVE MUST BE 4"ABOVE VACUUM SOURCE PORT WHEN X-VALVE IS MOUNTED HORIZONTALLY AND 12"ABOVE VACUUM SOURCE PORT COUPLINGS TARGET® <br /> WHEN MOUNTED IN THE VERTICAL POSITION. i <br /> 1. PRESSURE RATED PVC PIPE AND DWV PATTERN FITTINGS ONLY TO BE USED ON VACUUM SYSTEM. <br /> 6.THE CONNECTION FROM THE ACCUMULATOR SENSOR PORT TO THE CONTROLLER MUST NOT DIP BELOW TOP OF ACCUMULATOR OR CONTAIN ANY TRAPS. PIPE BRACING- CONTROLLER- 1000 N ICOLLET MALL <br /> SEE NOTE#3 OWNER FURNISHED MINNEAPOLIS, MN 55403 <br /> 2. PITCH VACUUM DRAINAGE PIPING AT A MINIMUM 1/4"per foot. TOP OF REFRIGERATED CASE SE VA VL SEE NOTE#2 <br /> 3. VACUUM DRAINAGE RISER MUST ENTER MAINS FROM ABOVE USING A WYE FITTING. THE WYE FITTING MAY BE ROLLED 45-FROM VERTICAL. <br /> 0 0 <br /> 4. NO TEE FITTINGS ARE PERMITTED IN THE VACUUM DRAINAGE PIPING. <br /> 0 0 _ <br /> 5. INSIDE PIPING SURFACES AND JOINTS MUST BE SMOOTH, FREE OF BURRS AND OBSTRUCTIONS. 24"MAX. <br /> L�k 1/4"I.D. FLEXIBLE RUBBER <br /> 6. LOCATE CLEAN OUTS IN THE VACUUM DRAINAGE PIPING AT THE ENDS OF MAINS AND BRANCHES,AND WHEN THERE IS A 90-CHANGE IN DIRECTION IN THE OVERHEAD BRANCH OR MAIN. ° ° TUBE TO CONTROLLER- <br /> 7. A SINGLE OFFSET IS ALLOWED IN VERTICAL RISERS.OFFSET IS NOT PREFERRED AND SHALL ONLY BE USED TO BYPASS STRUCTURAL OBSTRUCTIONS. 0 ° ° 21 OWNER FURNISHED,SEE NOTE#6 <br /> 8. ISOLATION AND CHECK VALVES SHALL BE FULL PORT VALVES. ° <br /> ° DC ENGINEERING <br /> 9. USE ONE DWV LONG SWEEP 1/4"BEND WHEN THERE ISA 90 DEGREE CHANGE IN DIRECTION. SEE NOTE#1. Careful listening. Dynamic solutions. <br /> cengineering.net <br /> 10. LAYOUT ILLUSTRATES GENERAL PIPING ARRANGEMENT.CONTRACTOR TO COORDINATE WITH GENERAL CONTRACTOR AND SPECIFIC INSTALLATION REQUIREMENTS FOR FINAL POINTS OF CONNECTION AND Phone:208.288.21 www.drengineering.net <br /> Project:l8TAR17 <br /> PIPE ROUTING. <br /> WHEN ACCUMULATOR IS CONCEALED AND NOT SERVICEABLE, <br /> EXTEND SENSOR PORT AND FURTHEST AIR INTAKE TO TOP OF loo ° <br /> CASES AND USE A WASTE FITTING AT THE BOTTOM OF AIR ° ° <br /> INTAKE FOR CLEANOUT ACCESS. <br /> CONNECTION TO G <br /> LIFT OR BRANCH MAIN (OSP MAXIMUM PERMISSIBLE ROTATION <br /> ANGLE OF WYE,TO FACILITATE <br /> CONNECTION TO LIFT AND BRANCH <br /> MAINS. <br /> X 45° 45° <br /> SENSOR PIPE 1 1/2"LIFT <br /> X <br /> VIEW X-X <br /> 0 0 <br /> EXTEND AIR INTAKE TO ° <br /> MATCH ELEVATION OF <br /> 1 CONNECTION OF LIFT BRANCH TO MAIN CASE DRAIN OUTLET <br /> Date P431 SCALE: 1/8"= V-0" <br /> No. Description <br /> 01/17/19 ISSUED FOR PERMIT <br /> CLEANOUT USE DWV COMBO <br /> FITTING FOR CLEANOUT <br /> ACCESS <br /> BRACING(TYPICAL) <br /> 0 0 loo 0 <br /> N <br /> LOPE MAINS OR BRANCHES <br /> /4"PER 12" <br /> CONDENSATE <br /> 36"MAX. <br /> FLOW 45° FLOW — 12 <br /> SLOPE Fol <br /> TO VAC CENTER <br /> 1/4" -------- 12" <br /> 1 1/2"PIPE ' <br /> 12" FLOW 48"MAX. <br /> 2 TYPICAL SLOPE DETAIL 3 SLOPE MAKE UP DETAIL 4 TYPICAL PIPE ACCUMULATOR CONNECTION <br /> P431 SCALE: 1/8"= 1'-0" P431 SCALE: 1/8"= V-0" <br /> P431 SCALE: 1/8"= 1'-0" <br /> ALL PIPING MUST BE SUPPORTED, BRACED <br /> CLEANOUT REQUIRED AND SECURED TO RESIST THRUSTING FORCES <br /> AND MINIMIZED MOVEMENT. <br /> ALL PIPING MUST BE BRACED PER ACORNVAC <br /> SPECS OR PER LOCAL CODE REQUIREMENTS <br /> WHICHEVER IS MORE RESTRICTIVE. <br /> 36"MAX. <br /> ALL BRACING ASSEMBLIES MUST BE ATTACHED <br /> TO STRUCTURAL STEEL, RIGID STUDS, OR <br /> o <br /> WOODEN BACKINGS.DRYWALL AND HVAC <br /> FLOW DUCT WORK ARE NOT ACCEPTABLE ANCHOR BEAM CLAMP WITH ANGLE BRACKET WITH <br /> MAINTAIN SLOPE POINTS. ALL THREAD&SPLIT ALL THREAD&SPLIT <br /> NOTES: RING HANGER RING HANGER <br /> 1. INSTALL CONTROLLER AND EXTRACTION VALVE IN READILY ACCESSIBLE LOCATION FOR SERVICE. SWING CHECK VALVE BRACING OF HORIZONTAL PIPING SHOULD BEOWNER FURNISHED. IN FOUR FOOT INTERVALS WHEN INSTALLATION <br /> 2. INSTALL MINI CHECK VALVE WITHIN 6"OF VACUUM SOURCE PORT. IS DONE IN PVC,AND EIGHT FOOT INTERVALS <br /> FULL PORT ISOLATION VALVE. FURNISHED FOR COPPER,OR AS REQUIRED BY LOCAL q <br /> 3. IF THE TOTAL QUANTITY OF PRIMARY LIFTS EXCEEDS 6,CONTACT FACTORY OR AUTHORIZED REPRESENTATIVE FOR APPROVAL. AND INSTALLED BY PLUMBING CONTRACTOR. CODE. FE S1 <br /> INSTALL IN ACCESSIBLE LOCATION. °, ° ° �Q��Q�cO H. <br /> FLEXIBLE RUBBERT SAGGING OF THE PIPING BETWEEN SUPPORTS <br /> TUBE TO CONTROLLER MINI CHECK VALVE- T-0"MAX. i -0"MAX. IS NOT PERMITTED; 1/4"PER FOOT OF SLOPE IS 'Q n° p 31885 <br /> OWNER FURNISHED,TYP OWNER FURNISHED, TO BE MAINTAINED AT ALL TIMES. ° <br /> P: 12/31/19 <br /> SEE NOTE#2. 1-1/2" <br /> 12" 18"MAX SECONDARY LIFT LATERAL OR SEISMIC BRACING SHOULD BE ° q o q4 P <br /> ADDED EVERY 25'OR AS REQUIRED BY LOCAL 'Q ° • KHAN\� <br /> CODE WHICHEVER IS MORE RESTRICTIVE. . <o OF CAL\F <br /> (2ND STAGE) <br /> 0 <br /> WHEN A UNISTRUT TRAPEZE IS USED, PIPING ° 6 <br /> d <br /> MUST BE CLAMPED DOWN SECURELY. <br /> OFFSET NO DOUBLE VERTICAL LIFTS ARE TO BE SECURED IN SIX PIPE STAND WELDED BRACKET <br /> 25'MAX OBSTRUCTIONS OFFSET FOOT INTERVALS. <br /> DATE: 01/17/2019 EXP: 12/31/2019 <br /> BRACING IS REQUIRED AT THE TOP OF ALL <br /> OFFSET I OBSTRUCTIONS I \ VERTICAL LIFTS TO PREVENT HORIZONTAL AND <br /> TYP 12"HORIZONTAL \ / OBSTRUCTION LATERAL MOVEMENT. <br /> 1-1/2"PRIMARY LIFT,TYP. MAX <br /> (1ST STAGE) SEE NOTE#3. j / \ OFFSET / \ / AN APPROVED BRACING ASSEMBLY MUST BE o a ° • d a • 6 <br /> / INSTALLED WITHIN ONE FOOT OF EVERY <br /> \ / DIRECTIONAL CHANGE,ON BOTH SIDES OF THE o 0 0 = o <br /> OFFSETS IN EXCESS OF 12"MUST — FITTING. • Q • Q Q <br /> RUN HORIZONTALLY WITH SLOPE OFFSET 0 1 1 O <br /> INTO COLLECTION POCKET BEFORE AN APPROVED BRACING ASSEMBLY MUST BE <br /> RESUMING LIFT. (o <br /> JJ INSTALLED WITHIN ONE FOOT OF EVERY ' ^ <br /> d Q ACCUMULATOR EXTRACTION VALVE,ON BOTH THE INLET AND LU <br /> u , <br /> Q d d• THE OUTLET SIDE. STRUT&STRUT TRAPEZE WITH STRUT&STRUT <br /> 4 G ACCUMULATOR CLAMPS CLAMPS <br /> 5 TYPICAL TWO STAGE LIFT DETAIL 6 ROUTING AROUND HORIZONTAL AND VERTICAL OBSTRUCTIONS 7 TYPICAL BRACING DETAILS U <br /> P431 SCALE: 1/8"=V-0" P431 SCALE: 1/8"=1'-0" P431 SCALE: 1/8"=1'-0" <br /> a: < F_U <br /> Q <br /> U °C <br /> TOP OF REFRIGERATED CASECONTROLLER Ir0 <br /> i <br /> W <br /> 1 1/2"PRESSURE RATED <br /> PIPE(TYPICAL) <br /> 1/4"PER FOOT J <br /> PIPE SLOPE OVERHEAD MAIN TO VACUUM CENTER <br /> MUST BE 16 FEET ABOVE FINISHED <br /> SENSOR PIPE NOTE: 2"SWING CHECK VALVE FLOOR OR GREATER.SEE PIPING PLAN <br /> \ OWNER FURNISHED, FOR PRESSURE RATED PIPE SIZE, BY <br /> / CLEANOUT 1.ALL COMPONENTS SHALL BE ACCESSIBLE FOR SERVICING. INSTALLED BY PLUMBING T-0"MAX. — PLUMBING CONTRACTOR. Z <br /> PEI <br /> � CONTRACTOR. <br /> 2. EXTRACTION VALVES,CONTROLLERS,AND SWING CHECK VALVES SUPPLIED 2"PRESSURE RATED PIPE, Q <br /> II EXTRACTION VALVE BY OWNERS AND INSTALLED BY CONTRACTOR. <br /> PLUMBING CONTRACTOR Q <br /> I 3. REFER TO DETAILS ON SHEET P431 FOR ADDITIONAL INFORMATION. 1 1/2"ISOLATION VALVE (TYPICAL) <br /> I I I ABOVE ACT CEILING N <br /> I ` USE DWV COMBO FITTING 4. HEIGHT OF TWO AIR INTAKES MUST BE LOWER THAN THE INLET <br /> FOR CLEANOUT ACCESS OF ANY DRAINS IT IS CONNECTED TO. 1/4"PER FOOT <br /> 1 \ <br /> / PIPE SLOPE <br /> I / ACT CEILING <br /> CLEANOUT <br /> 1 1/2"PIPE ACCUMULATOR \ ° ° / 1 1/2"PRESSURE RATED <br /> PROVIDED BY CONTRACTOR. / PIPE RISER. RATED PIPE <br /> (TYPICAL).SEE DETAIL 5/P431. RISER BY PLUMBING <br /> �`� CONTRACTOR Project Number <br /> —0738 073 <br /> ij REFRIGERATED CASE REFRIGERATED CASE <br /> T-0"MAX. 1 1/2"PIPE DOWN TO PIPE Config: LL <br /> I — <br /> / 1/4"PER FOOT <br /> MAIN DRAIN LINE ACCUMULATOR.(TYPICAL) <br /> / Drawn By <br /> PIPE SLOPE <br /> B. SMEAD <br /> Checked By J. HAM M <br /> EXTRACTION VALVE <br /> (TYPICAL) <br /> I I REFRIGERATED CASE REFRIGERATED CASE CHECK VALVE <br /> / <br /> REFRIGERATED CASE CONDENSATE <br /> (TYPICAL) VACUUM DETAILS <br /> 8 TYPICAL TWO STAGE, MULTI-CASE, END DISCHARGE LIFT 69TOP VIEWOF CASES <br /> P431 SCALE: 1/8"= 1'-0" <br /> P431 SCALE: 1/8"= V-0" <br /> 1/17/2019 1 :23:02 PM <br />