rom" <br /> HECEIVED <br /> NOV 14 2014 <br /> _ 7. tINDER-DISPENSER CONTAINMENT(UDC)TESTING <br /> Test Method Developed By: ❑ UDC Manufacturer E Industry Standard ❑ Professional Ergineer <br /> ❑ Other(SpeciJiv <br /> Test Method Used: ❑Pressure ❑ Vacuum ® I Iydrostatic <br /> ❑ Other(Spec f,) <br /> ._...._._.__ _ _..____..... <br /> Test Equipment('sed: Incon Sump Tester ; Equipment Resolution. +J-0.002" <br /> __ UDC#9110 UDC# 11/12 UDC# 13/14 UDC# 15/16 <br /> UDC Manufacturer: _ western Fiberglas Western Fiberglass Western_Fiberglass Western Fiberglass <br /> UDC Material: _ Fiberglass Fiber lass Fiberglass Fiberglass <br /> UDC Depth: 31" 31" 31" 31" <br /> Height from UDC Bottom to'fop s., 5.. 5.• 5" <br /> of Highest Piping Penetration: <br /> I Leight from UDC Bottom to <br /> Lowest Electrical Penetration: _ t0 10 1q" I0" <br /> — <br /> Condition of 1JDC prior to Good Good Good Good <br /> lectin«: <br /> " Portion of UDC Tested —2_above i ing 2'*above piping _ 2"above piping 2"above jpji g <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ❑Yes❑No 0 NA ❑Yes❑No ®NA ❑ Yes❑No ®NA ❑Yes❑No 0 NA <br /> product and water)?' _ <br /> Turbine shutdown response time N/A N/A N/A NiA <br /> Is system programmed for fail- <br /> sate shutdown? ❑Yes El No ®NA C)Yes❑No ®NA ❑Yes❑No ®NA ❑Yes❑No ®NA <br /> Was fail-safe verified to be 0 Yes❑No ®NA 0 Yes❑No ®NA ❑Yes❑No ®NA ❑Yes❑No ®NA <br /> o erationalf <br /> Wait time between applying <br /> i pressure/vacuumhvater and 30 minutes 30 minutes 30 minutes 30 minutes <br /> starting test <br /> Test Stan Time: 12:32 pin 12:32 pm 1:30 pni 10:36 am <br /> Initial Reading Ra): 2.4553 3.9879 2.5442 2.3052 <br /> Test End Time: 12:47 pm 12:47 prn 1:45 pin 10:51 am <br /> Final Reading(RF): 2.4551 3.9880 2.5439 2.3053 <br /> Test Duration: Is min. 15 min. �15 min. IS min. <br /> Change in Reading Rr-Ri): 0.0002 0.0001 _ 0.0003 0.0001 <br /> Pass/Fail Threshold or Criteria: +/-0.002" +/-0.002" +/-0,002'• +/_0.002" <br /> Test Result: © Pass 0 Fail ® Pass 0 Fail ® Pass 0 Fail ® Pass 0 Fail <br /> Was sensor removed for testing? ®Yes❑No❑NA ®Yes❑No❑NA 0 Yes❑No ❑NA ®Yes❑No❑NA <br /> Was sensor properly replaced and <br /> verified functional after testin ? ®Yes❑No[INA ®Yes❑No❑NA ®Yes C1No[INA ®Yes❑No❑NA <br /> Comments—(include hiformation on repairs made prior to testing, and recoinniended follow-up far failed tests) <br /> "Sensor functionality was not confirmed.This procedure is not part of the Secondary Containment testing scope of work". <br /> ' If the entire depth of the UDC is not tested,specitp how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRC13 LG-160) <br />