Laserfiche WebLink
am <br /> Maintenance History Service Station Systems <br /> 680 Quinn Ave. <br /> Shell 135997 San Jose,CA 95112 <br /> 1455 The Alameda @ Hester in San Jose License#:485184 <br /> 8/14/14 to 11/14/14 <br /> Job# Release Ref# Finished Tech Hold Status Tasks <br /> 707567 Need 11/14/14 Support Checked-in Sensor-ISD Pressure,Warn-Gross PSI,Cleared Alarm(Winter Fuel)[1104 10AM]; <br /> Dispatch: 11/14/14 MSS: Emailed to:Support@ service stat ionsystems.com; <br /> 706722 Ethan Lim / ! DaveT Scheduled Designated Operator Insp,Compliance,; <br /> 706469 Ethan 11/7114 Support Invoiced Sensor-ISD Pressure,Warn-Gross PSI,Cleared Alarm(Winter Fuel); <br /> 'Dispatch: 1117114 O?E:Emailed to:Support@servicestationsystems.com; <br /> 1117114 O?E: Ethan reports gross psi warn <br /> 703768 Ethan 10/17/14 PauIR Invoiced Disp#03, Meter-ISD Vpr Flow,Warn-Gross Collect,Passed w/Repairs[1-13]: <br /> Dispatch: 10/16/14 O?E:Ethan reports H3/H4 Gross collect warn this morning Vapor to Liquid Test,Verification,Passed w/Repairs; <br /> at Gam today. Ethan accepted same day expedite fee.HE HAS HIS OWN Nozzle Bag Test,Verification,Not Required; <br /> HANGING HARDWARE ON SITE. VP-1000 Vac Motor Test,Verification;Passed Test; <br /> Disp#04, Meter-ISD Vpr Flow,Warn-Gross Collect,Passed w/Repairs[H4]; <br /> Disp#04,Vapor Motor,Alarm-ISD,Replaced(Same Model), <br /> 'Tech: 10117/14 PJR:troubleshot isd gross colects on 3/4 to bad motor, <br /> replaced,tested,disp 4 95,disp 3 after adj 1.06,all ok,cleared alarms- <br /> *Billing: 10/20/14 ARJ:Work Order 1377692 to billing <br /> 703666 Ethan Lim 10124/14 DaveT Invoiced Designated Operator Insp,Compliance.Passed Verification; <br /> Tech: 10/24/14 MSS:Completed D.O inspection <br /> Billing. 1114114 ARJ:WO 1377573 to April <br /> 703592 Need ! i Waiting Healy Qtr Insp,Compliance,; <br /> Billing: 10/11113 DLW:Flat-150.00 <br /> 701144 Need / 1 BryanKe Cust. Hold Disp#01,Vapor Recovery, Preventative Maint.,; <br /> 'Dispatch:9125/14 JPP:Ethan has approved SSS to replace the vapor return <br /> hose between the vapor shear valve and flex line with copper tubing on disp <br /> 1/2,516,7/8. Flat rate$600.00 <br /> 700460 Ethan 9125/14 AlexB Invoiced Sensor-ISD Pressure,Warn-Vapor Leak,Reset[9/19 6AM]; Z <br /> i <br /> /R <br /> d Pwepars; <br /> Verification,Passed Dispatch:9124/14 O?E:Ethan approved 10"WC Test.Two tech's and lift. Static Pres.2 in.WC Test.Ver < <br /> Notified Brian P.Scheduled for Thursday 9!25 Tank#03,Vapor Adapter,Damaged/Worn,Replaced(Same Model). <br /> Tank#01,TLM Cap,Damaged/Worn,Replaced(Same Model); r'a C) <br /> 9124!14 O?E Emailed to: Tank#01,Vent PV Valve, Damaged,NVorn.Replaced(Same Model). h Z <br /> general@AbleMaintenance.com;brian@ablemaintenance.com,Ryan@Servicesta +tr CD <br /> C <br /> tionsystems com; <br /> 9/19114 JIT:Fourth trip for ISD Vapor leak.First tech Bryan,8/31/14 BEK _ i� <br /> Replaced damaged hose disp 6,damaged nozzle bellows disp 4. Ran St-30, 1 � <br /> fail. Found vapor flex hose disp 516 split between vapor shear valve and f/g <br /> vapor return line Spoke with Joey,Mark. Need to return ASAP to repair, o <br /> replace vapor return hose. Reset vlw per Mark. Informed mgr will need to ) - <br /> return Second tech,Bryan,919/14 BEK:Replaced worn rubber vapor hose disp <br /> ni <br /> 1/2.5/6,7/8 with copper piping Disp 3/4 not done..rubber hose newer han r, y <br /> Printed by DebbieW at 11/14/14 2.05pm Page-1- <br />