am
<br /> Maintenance History Service Station Systems
<br /> 680 Quinn Ave.
<br /> Shell 135997 San Jose,CA 95112
<br /> 1455 The Alameda @ Hester in San Jose License#:485184
<br /> 8/14/14 to 11/14/14
<br /> Job# Release Ref# Finished Tech Hold Status Tasks
<br /> 707567 Need 11/14/14 Support Checked-in Sensor-ISD Pressure,Warn-Gross PSI,Cleared Alarm(Winter Fuel)[1104 10AM];
<br /> Dispatch: 11/14/14 MSS: Emailed to:Support@ service stat ionsystems.com;
<br /> 706722 Ethan Lim / ! DaveT Scheduled Designated Operator Insp,Compliance,;
<br /> 706469 Ethan 11/7114 Support Invoiced Sensor-ISD Pressure,Warn-Gross PSI,Cleared Alarm(Winter Fuel);
<br /> 'Dispatch: 1117114 O?E:Emailed to:Support@servicestationsystems.com;
<br /> 1117114 O?E: Ethan reports gross psi warn
<br /> 703768 Ethan 10/17/14 PauIR Invoiced Disp#03, Meter-ISD Vpr Flow,Warn-Gross Collect,Passed w/Repairs[1-13]:
<br /> Dispatch: 10/16/14 O?E:Ethan reports H3/H4 Gross collect warn this morning Vapor to Liquid Test,Verification,Passed w/Repairs;
<br /> at Gam today. Ethan accepted same day expedite fee.HE HAS HIS OWN Nozzle Bag Test,Verification,Not Required;
<br /> HANGING HARDWARE ON SITE. VP-1000 Vac Motor Test,Verification;Passed Test;
<br /> Disp#04, Meter-ISD Vpr Flow,Warn-Gross Collect,Passed w/Repairs[H4];
<br /> Disp#04,Vapor Motor,Alarm-ISD,Replaced(Same Model),
<br /> 'Tech: 10117/14 PJR:troubleshot isd gross colects on 3/4 to bad motor,
<br /> replaced,tested,disp 4 95,disp 3 after adj 1.06,all ok,cleared alarms-
<br /> *Billing: 10/20/14 ARJ:Work Order 1377692 to billing
<br /> 703666 Ethan Lim 10124/14 DaveT Invoiced Designated Operator Insp,Compliance.Passed Verification;
<br /> Tech: 10/24/14 MSS:Completed D.O inspection
<br /> Billing. 1114114 ARJ:WO 1377573 to April
<br /> 703592 Need ! i Waiting Healy Qtr Insp,Compliance,;
<br /> Billing: 10/11113 DLW:Flat-150.00
<br /> 701144 Need / 1 BryanKe Cust. Hold Disp#01,Vapor Recovery, Preventative Maint.,;
<br /> 'Dispatch:9125/14 JPP:Ethan has approved SSS to replace the vapor return
<br /> hose between the vapor shear valve and flex line with copper tubing on disp
<br /> 1/2,516,7/8. Flat rate$600.00
<br /> 700460 Ethan 9125/14 AlexB Invoiced Sensor-ISD Pressure,Warn-Vapor Leak,Reset[9/19 6AM]; Z
<br /> i
<br /> /R
<br /> d Pwepars;
<br /> Verification,Passed Dispatch:9124/14 O?E:Ethan approved 10"WC Test.Two tech's and lift. Static Pres.2 in.WC Test.Ver <
<br /> Notified Brian P.Scheduled for Thursday 9!25 Tank#03,Vapor Adapter,Damaged/Worn,Replaced(Same Model).
<br /> Tank#01,TLM Cap,Damaged/Worn,Replaced(Same Model); r'a C)
<br /> 9124!14 O?E Emailed to: Tank#01,Vent PV Valve, Damaged,NVorn.Replaced(Same Model). h Z
<br /> general@AbleMaintenance.com;brian@ablemaintenance.com,Ryan@Servicesta +tr CD
<br /> C
<br /> tionsystems com;
<br /> 9/19114 JIT:Fourth trip for ISD Vapor leak.First tech Bryan,8/31/14 BEK _ i�
<br /> Replaced damaged hose disp 6,damaged nozzle bellows disp 4. Ran St-30, 1 �
<br /> fail. Found vapor flex hose disp 516 split between vapor shear valve and f/g
<br /> vapor return line Spoke with Joey,Mark. Need to return ASAP to repair, o
<br /> replace vapor return hose. Reset vlw per Mark. Informed mgr will need to ) -
<br /> return Second tech,Bryan,919/14 BEK:Replaced worn rubber vapor hose disp
<br /> ni
<br /> 1/2.5/6,7/8 with copper piping Disp 3/4 not done..rubber hose newer han r, y
<br /> Printed by DebbieW at 11/14/14 2.05pm Page-1-
<br />
|