3G; <br /> YE <br /> project No. 90161.e <br /> 7 June 1990 <br /> Moderately expansive soils should be compacted to at least 870 <br /> not more than 92% relative compaction an <br /> relative compaction but <br /> d <br /> at a moisture content at least 3% over optimum. Degree of <br /> compaction is the ratio of the dry density of the constructed <br /> w fill to the maximum determined by the ASTM Test Procedure D1557- <br /> 78. <br /> 5.13 Compaction shall be by sheepsfoot rollers or other types of <br /> acceptable compacting rollers. Rollers shall be of such design <br /> that they will be able to compact the fill to the specified <br /> density. Rolling shall be accomplished while the fill material <br /> ed moisture content range. Rolling of each <br /> is within the specifi <br /> layer shall be continuous over the entire area and the roller <br /> shall make sufficient trips to ensure that the required density <br /> y has been achieved. No ponding <br /> jetting shall be permitted. <br /> 5.14 Field density tests shall be performed at }east every 2 <br /> feet of compacted fill height by the Geotechnical Engineer in <br /> Accordance with ASTM Test Procedure D1556-82 or ASTM Test <br /> Procedure D2922-81. When sheepsfoot rollers are used for <br /> compaction, the density tests shall be taken in the compacted <br /> material below the surface disturbed by the roller. When these <br /> tests indicate that the density of any layer of fill or portion <br /> thereof is below the required compaction, it shall b;� reworked � <br /> until than required compaction has been achieved. <br /> 5.15 No shall be placed or compacted either during periods <br /> " of rain or on ground which is not drained of all free water. <br /> 26 <br />