Laserfiche WebLink
Page 4 of 7 <br /> 6. PIPWG SUMP TESTING <br /> Test Method Developed By: rl Sump Manufacturer X Industry Standard ❑Professional Engineer <br /> 0 Other(4pec fy) <br /> Test Method Used: F-1 Pressure 0 Vacuum X Hydrostatic <br /> rl Other(Specify) <br /> Test Equipment Used:Incon TS-STS Equipment Resolution: <br /> Sump#P.P.S. Sump#R.P.S. Sump# Sump# <br /> Sump Diameter: 42» 4211 <br /> Sump Depth: 62" 64" <br /> Sump Material; Fiberglass Fiberglass <br /> Height from Tank Top to Top of 12» l2" <br /> H est.Pi in Penetration_ <br /> Height from Tank Top to Lowest 22„ 23" I <br /> EIectrical.Penetration: <br /> Condition,of sump prior to testing: Clean Clean <br /> Portion of Sump Tested' Bottom Bottom <br /> Does turbine shut down when <br /> sump sensor detects liquid(both X Yes ❑ No ❑NA X Yes ❑No CNA ❑Yes 0 No [INA ❑Yes ❑No I''�NA <br /> roduct and water)7 <br /> Turbine shutdown response time 2 Seconds 2 seconds <br /> Is system programmed for fail-safe X Yes ❑No ❑NA X Yes ❑ No ❑NA 0 Yes ❑No �NA ❑Yes F1 No ❑NA <br /> shutdown?` <br /> Was fail-safe verified to be XYcs n No ❑NA X Yes ❑ No 0 NA ❑Yes ❑No ❑NA X Yes <br /> o erational?" ❑No 11 NA <br /> Wait time between applying <br /> pressure/vaeu.um/water and starting 15 minutes 15 minutes <br /> test: <br /> Test Start Time: 9:24 am 9:24 am <br /> Initial.Reading(RO: 1.7399" 0.7114" <br /> Test End Time: 9:40 am 9:40 am <br /> Final.Reading(RF): 1.7397" 0.7097" <br /> Test Duration.: 16 minutes 16 minutes <br /> Change in Reading(RF-Ri): .0001" loss .0017"loss <br /> Pass/Fail Threshold or Criteria: Loss<.002"=pass Lass<.002"=pass <br /> Teat Result: X Pass ❑Fail X Pass ❑Fail 0 Pass Cl Fall ❑ Pass ❑Feil <br /> Was scnsor removed for testing? X Yes 0 No ❑NA X Yes ❑No ❑NA fl Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> Was sensor properly replaced and <br /> verified functional after testing? 11X Yes ❑No 0 NA X Yes ❑No ❑NA 0 Yes No 0 NA 0 Yes 0 No ❑NA <br /> Comments—(include information on repairs made prior to tmlin.Z and recommended follow-up for failed tests) <br /> Unable to baring vyater over the Dininl� Denetratl"ons duet lack of test boots. <br /> If the entire depth of the sump is not tested, specify how much was tested. If the answer to my y of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (Sec SWRCB LG-160) <br />