Laserfiche WebLink
SWRCB, January 2002 <br />5. SECONDARY PIPE TESTING <br />Test Method Developed By: ❑ Piping Manufacturer ® industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ® Pressure ❑ Vacuum ❑ Hydrostatic <br />❑ Other (Specify) <br />Test hquipment Used: 0 —15 PSI GAUGES Equipment Resolution: 0.002" <br />nlI( <br />0 7 291' <br />ENVIRONN, <br />._ , <br />Piping Run # T-4 87 <br />Product Line <br />Piping Run # T-5 91 <br />Product Line <br />Piping Run # T-4 87 <br />Vent Line <br />Piping Run # T-5 91 <br />Vent Line <br />Piping Material: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />.............. <br />Piping Manufacturer: <br />. <br />A.O.Smith <br />A.O.Smith <br />A.O.Smith <br />A.O.Smith <br />Piping Diameter: <br />3" over 2" <br />3" over 2"' <br />3" over 2" <br />3" over 2" <br />Length of Piping Run: <br />Approx. 75' <br />Approx. 55' <br />Approx. 45' <br />Approx. 55' <br />Product Stored: <br />87 unleaded <br />91 Premium <br />87 unleaded <br />91 Premium <br />Method and location of <br />piping -run isolation: <br />Termination Fitting <br />@ STP Sump <br />Termination Fitting <br />@ STP Sump <br />Termination Fitting <br />@ Fill Sump <br />Termination Fitting <br />@ Fill Sump <br />Wait time between applying <br />pressure/vacuum/water and <br />test: <br />10 min <br />10 min <br />10 min <br />10 min <br />-starting <br />Test Start Time: <br />8:45am <br />8:45am <br />8:45am <br />8:45am <br />Initial Reading (RI): <br />5.Opsi <br />5.0psi <br />5.Opsi <br />5.Opsi <br />Test End Time: <br />9:45am <br />9:45am <br />9:45am <br />9:45am <br />Final Reading (RF): <br />5.Opsi <br />S.Opsi <br />5.0psi <br />5.0psi <br />Test Duration: <br />1 hr <br />1 hr <br />1 hr <br />1 hr <br />Change in Reading (RF -RI): <br />O.Opsi <br />O.Opsi <br />O.Opsi <br />0.0psi <br />Pass/Fail Threshold or <br />Criteria: <br />NO LOSS <br />NO LOSS <br />NO LOSS <br />NO LOSS <br />Test Result: <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />Comments — (include information on repairs made prior to testing and recommended follow-up for failed tests) <br />nlI( <br />0 7 291' <br />ENVIRONN, <br />._ , <br />