MONIT*ING SYSTEM CERTIFWATION <br /> CERTIFICATION / TEST DATE: August 1, 2006 <br /> Al. FACILITY A2. OWNER <br /> Name 99 Shell Name Angle Enterprises <br /> Address 7700 Moreland Court,Stockton, CA 95212 Address 35584 Conavan Lane, Fremont, CA 94536 <br /> Phone# 209-939-1906 Phone# 510-552-4822 <br /> Contact Balaji Angle Contact Balaji Angle <br /> D. RESULTS OF TESTING / SERVICING <br /> Make / Model of Monitoring System: Veeder-Root TLS-350 <br /> Software Version Installed: 324.02 <br /> Complete the following checklist: <br /> ■ Yes ❑ No* Is the audible alarm operational? <br /> ■ Yes ❑ No* Is the visual alarm operational? <br /> ■ Yes ❑ No* Were all sensors visually inspected,functionally tested,and confirmed operational? <br /> ■ Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment <br /> will not interfere with their proper operation? <br /> ❑ Yes ❑ No* If alarms are relayed to a remote monitoring station,Is all communications equipment(e.g.modems) <br /> ■ N/A operational? <br /> ■ Yes ❑ No* I For pressurized piping systems,does the turbine automatically shut down If the piping secondary containment <br /> ❑ N/A monitoring system detects a leak,fails to operate,or Is electrically disconnected? If yes:which sensors Initiate <br /> positive shutdown? (check all that apply) ■ Sump/Trench sensors; ■ Dispenser Containment Sensors. <br /> ■ Yes ❑ No* Did you confirm positive shut-down due to leaks and sensor failure/disconnection? <br /> ❑ Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e.no <br /> ■ N/A mechanical overfill prevention valve is installed),Is the overfill warning alarm visible and audible at the tank <br /> fill point(s)and operating properly? If so,at what percent of tank capacity does the alarm trigger? °% <br /> ❑ Yes* ■ No Was any monitoring equipment replaced? If yes,Identify specific sensors,probes,or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts In Section E,below. <br /> ■ Yes* ❑ No Was any liquid found inside any secondary containment systems designed as dry systems? <br /> (Check all that apply) ■ Product; ■ Water. If yes,describe causes in Section E,below. <br /> ■ Yes ❑ No* Was monitoring system set-up reviewed to Insure proper settings? Attach set-up reports,N applicable. <br /> ■ Yes ❑ No* Is all monitoring equipment operational per manufacturer's specifications? <br /> * In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. COMMENTS <br /> Fill sumps, STP sumps and UDC's are all double wall and brine filled. All have Veeder-Root model 0794380-322 sensors. <br /> The vent transition box is double wall and brine filled with Veeder-Root model 0794380-208 and 0794380-322 sensors. <br /> The continuos vacuum on the secondary lines is monitored with Veeder-Root model 0330020-408 smart sensors. <br /> Diesel and 91 tanks are a split tank with a single annular. <br /> Found diesel leak in dispenser 5-6. <br /> Found liquid in 87 STP sump. <br /> 2006 Walton Engineering,Inc. <br /> Page 2 of 3 <br />