Laserfiche WebLink
SPILL CONTAINER CONTAINMENT TESTING <br /> Test Method By: Manufacturer • Industry Standard Professional Engr. Other(see below) <br /> Test Method Uses: Pressure vacuum • Hydrostatic Other(see below) <br /> Measuring Equipment Used: Level Change Indicator (Caldwell System 2001 /Walton Engineering) <br /> Description Tank#1 Tank#2 Tank#3 <br /> Spill container manufacturer OPW OPW _ OPW <br /> Spill container capacity (US gallons) 5 Gallons 5 Gallons 5 Gallons _ <br /> Spill container depth (inches) 15.00 14.00 17.50 <br /> Product contained Gasoline-87 Gasoline-91 Diesel <br /> Is Spill container located in a sump? Yes Yes Yes <br /> Does sump have a liquid sensor installed? Yes Yes Yes <br /> Distance between fill adapter and 16" 16" N/A <br /> vapor adapter centers (inches) <br /> Condition of spill container prior to testing Dry Dry Dry <br /> Portion of spill container tested Entire Entire Entire <br /> Wait time for water level to stabilize (hr:min) 0:05 0:04 0:06 <br /> Depth of water level from bottom (inches) 14.75 13.75 17.25 <br /> Test start time 10:50 AM 10:51 AM 11:05 AM <br /> Test end time 11:20 AM 11:21 AM 11:35 AM <br /> Test duration (hr:min) 0:30 0:30 0:30 <br /> Change in water level (t 0.000 inches) 0.000 0.000 0.000 <br /> Pass/Fail threshold (0.005 inches/%Hr.) 0.005 0.005 0.005 <br /> TEST RESULT PASS PASS PASS <br /> MM <br /> Comments: <br /> © 2003 Walton Engineering,Inc. <br />