Laserfiche WebLink
UNDER DISPENSER CONTAINMENT (UDC) TESTING <br /> Test Method By: Manufacturer • Industry Standard Professional Engr. Other(see below) <br /> Test Method Uses: Pressure vacuum • Hydrostatic Other(see below) <br /> Measuring Equipment Used: INCON TS-STS (Electronic Sump Test System) <br /> Description Disp# 1/2 Disp#3/4 Disp#5/6 Disp#7/8 <br /> UDC manufacturer Total Containment Total Containment Total Containment Total Containment <br /> UDC material FRP FRP FRP FRP <br /> UDC depth (inches) 28" 28" 28" 28" <br /> Height from UDC bottom to highest 10" 10" 10" 10" <br /> piping penetration <br /> Height from UDC bottom to lowest 4" 4" 4" 4" <br /> electrical penetration <br /> Type of shut-down resent Sensor Sensor Sensor Sensor <br /> Condition of UDC prior to testing Dry Dry Dry Dry <br /> Portion of UDC tested Entire Entire Entire Entire <br /> Was sensor removed for testing? Yes Yes Yes Yes <br /> Was sensor properly replaced after testing? Yes Yes Yes Yes <br /> Wait time for water level to stabilize (hr:min) 0:10 0:10 0:10 0:10 <br /> Depth of water level from UDC bottom (in.) 12" 12" 12" 12" <br /> Test start time 8:59 AM 8:59 AM 8:59 AM 8:59 AM <br /> Test end time 9:14 AM 9:14 AM 9:14 AM 9:14 AM <br /> Test duration (hr:min) 0:15 0:15 0:15 0:15 <br /> Change in water level (t 0.000 inches) 0.000 0.001 0.000 0.001 <br /> Pass/Fail threshold (0.005 inches/%s Hr.) 0.005 0.005 0.005 0.005 <br /> TEST RESULT PASS PASS PASS PASS <br /> Comments: <br /> s 2003 Walton Engineering,Inc. <br />