Laserfiche WebLink
SECTION 10520 <br /> 3 FIREFIGHTING DEVICES <br /> 4 <br /> s <br /> 6 PART 1: GENERAL <br /> 7 <br /> 8 1.01 DESCRIPTION <br /> 9 <br /> o The work of this Section consists of furnishing and installing portable fire extinguishers and <br /> >> mounting hardware. <br /> 12 <br /> 13 1.02 OUALITY ASSURANCE <br /> is <br /> 15 Laboratory Testing and Approval: Firefighting device shall be Underwriters Laboratories <br /> 16 tested, approved and labelled. <br /> n <br /> 18 Equipment shall be standard equipment of a recognized manufacturer regularly engaged <br /> 19 in production of firefighting equipment, and shall be of such type as to be readily <br /> 20 recharged, serviced and/or maintained by local fire equipment distributors. <br /> 21 <br /> 22 PART 2: MATERIALS <br /> 1 23 <br /> 24 2.01 PORTABLE FIRE EXTINGUISHERS (FE) <br /> 2s <br /> 1 26 A. TYPE 1: U/L 2A-10B:C, Multi-purpose dry chemical, 5-pound minimum capacity; enameled <br /> 27 steel finish; manufacturer's standard wall mounting bracket; front-reading pressure gauge; <br /> 28 fully charged and tagged. J. L. Industries "Cosmic 5E"; Larsen's MP5, or equal. <br /> 29 <br /> 30 <br /> 31 PART 3: EXECUTION <br /> 32 <br /> 33 3.01 INSTALLATION <br /> 34 <br /> 35 Locate bracket so that topmost point of extinguisher will not be more than 60 inches above <br /> 36 finish floor line. Secure to wall or surface shown on Drawings per manufacturer's <br /> 37 recommendations. <br /> 38 <br /> 39 <br /> 40 END OF SECTION <br /> FIREFIGHTING DEVICES <br /> 042894 10520-1 <br />