My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2010-2018
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
K
>
KETTLEMAN
>
1301
>
2300 - Underground Storage Tank Program
>
PR0231342
>
COMPLIANCE INFO_2010-2018
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
11/4/2021 4:04:58 PM
Creation date
6/3/2020 9:46:56 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2010-2018
RECORD_ID
PR0231342
PE
2361
FACILITY_ID
FA0000392
FACILITY_NAME
FLAMES LIQUOR
STREET_NUMBER
1301
Direction
W
STREET_NAME
KETTLEMAN
STREET_TYPE
LN
City
LODI
Zip
95242
APN
03104030
CURRENT_STATUS
01
SITE_LOCATION
1301 W KETTLEMAN LN
P_LOCATION
02
P_DISTRICT
004
QC Status
Approved
Scanner
SJGOV\rtan
Supplemental fields
FilePath
\MIGRATIONS\UST\UST_2361_PR0231342_1301 W KETTLEMAN_2010-2018.tif
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
353
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
C <br />SWRCB, January 2002 Page of <br />7. UNDER -DISPENSER CONTAINMENT (UDC) TESTING <br />Test Method Developed By: <br />❑ UDC Manufacturer <br />❑ Industry Standard X Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: <br />❑ Pressure <br />❑ Vacuum <br />X Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Caldwell Level Change Indicator <br />Equipment Resolution: <br />.002 <br />UDC # 1&2 <br />UDC # 3&4 <br />UDC # 5&6 <br />UDC # 7&8 <br />UDC Manufacturer: <br />Bravo <br />Bravo <br />Bravo <br />Bravo <br />UDC Material: <br />Coated Steel <br />Coated Steel <br />Coated Steel <br />Coated Steel <br />UDC Depth: <br />10" <br />10" <br />10" <br />10" <br />Height from UDC Bottom to Top <br />Enters From Bottom <br />Enters From Bottom <br />Enters From Bottom <br />Enters From Bottom <br />of Highest Piping Penetration: <br />Height from UDC Bottom to <br />Enters From Bottom <br />Enters From Bottom <br />Enters From Bottom <br />Enters From Bottom <br />Lowest Electrical Penetration: <br />Condition of UDC prior to <br />Dry <br />Dry <br />Dry <br />Dry <br />testing: <br />Portion of UDC Tested <br />Water Level 7" <br />Water Level 7" <br />Water Level 7" <br />Water Level 7" <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />Yes X No ❑ NA <br />Yes X No ❑ NA <br />Yes X No ❑ NA <br />Yes X No ❑ NA <br />product and water)? * <br />Turbine shutdown response time <br />N/A <br />N/A <br />N/A <br />N/A <br />Is system programmed for fail- <br />X Yes ElNo ElNA <br />X Yes ElNo 11NA <br />X Yes ❑ No ❑ NA <br />X Yes ❑ No ElNA <br />safe shutdown? <br />Was fail-safe verified to be <br />❑ yes X No ❑ NA <br />❑ Yes X No ❑ NA <br />❑ Yes X No ❑ NA <br />❑ Yes X No ❑ NA <br />o erationalf <br />Wait time between applying <br />5 Minutes <br />5 Minutes <br />5 Minutes <br />5 minutes <br />water and starting test <br />Test Start Time: <br />9:35 <br />9:40 <br />9:55 <br />10:00 <br />Initial Reading (111): <br />.001 <br />.001 <br />.001 <br />.001 <br />Test End Time: <br />1 10:05 <br />10:10 <br />10:25 <br />10:30 <br />Final Reading (RF): <br />.001 <br />.001 <br />.001 <br />.001 <br />Test Duration: <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />Chane in Readin RF -RI : <br />0 <br />0 <br />0 <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005/30 Minutes <br />.005/30 Minutes <br />.005/30 Minutes <br />.005/30 Minutes <br />Test Result: <br />X :! Pass Cl Fail <br />X Pass 0 Fail <br />X Pass 0 Fall' <br />X Pass ❑ Fail <br />Was sensor removed for testing? <br />X Yes ❑ No ❑ NA <br />X Yes 11No ❑ NA <br />X Yes 11No 11NA <br />X Yes 11No ElNA <br />Was sensor properly replaced and <br />X Yes ❑ No Ll NA <br />X Yes ❑ No ❑ NA <br />X Yes []No 11NA <br />X Yes 11 No El NA <br />verified functional after testin ? <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />1 If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />
The URL can be used to link to this page
Your browser does not support the video tag.