Veeder-Root Line Leak Appliclin Guide • <br /> 4. Locate red switch bank labeled S1 on the CPT's Controller CPU board,and verify that dip switch 2 is set to the Closed <br /> position (to enable the PLLD precision line leak function),and dip switch 8 is set to the Open position (to disable the CPT's <br /> line leak function). <br /> 5. Verify that the Rotary Pressure Dial,also on the CPT's Controller CPU board,is set to either the 2(24 psi),3(27 psi),4(30 <br /> psi),5(33 psi),or 6(36 psi)position. <br /> O` 1 <br /> pI1d/cptp11d.eps <br /> ti <br /> tl` <br /> i------- --- <br /> IL t.1 • <br /> • II j DPLLD or PLLD <br /> O. transducer <br /> II DPLLD or PLLD d Only ;i <br /> p transducer � <br /> in SwiftCheck L J <br /> t0 O Valve :O SpikeCheck <br /> Valve Assy. <br /> � OFunctional <br /> Element <br /> Red Jacket Standard CPT Red Jacket Quantum CPT <br /> Transducer Installation - Red Jacket Big-Flo Pumps, Red Jacket Maxxum Pumps and FE Petro <br /> High Capacity Pumps <br /> BIG-FLO PUMPS <br /> 1. You will need to install a reducing tee(customer supplied)in either of the 3-inch discharge ports of the pump with the 2- <br /> inch opening facing up. If you have the room, it may be easier to install this tee between the Pressurstat kit and the unused <br /> port instead of in the discharge line(as shown in the figure below).Alternatively,the DPLLD or PLLD transducer can be <br /> installed in the leak detector port of a Big-Flo leak detector if it is already present in the line(as shown in the figure below). <br /> 2. Install the Red Jacket Big-Flo Pressurstat Kit(Red Jacket part number 144-314-5)following the instructions with the kit. <br /> 3. Thread the DPLLD or PLLD transducer into the 2-inch opening of the tee. <br /> QIMPORTANT!Seal any pipe threads using a UL-classified,nontoxic pipe sealant suitable for the fuel involved. <br /> 4. Verify that the TLS-350 Series Console has Version x19 or later(TLS-450 Series Console has Version 1 or later)software. <br /> Junction box <br /> OPTIONAL INSTALLATION EXAMPLE (customer supplied) <br /> 3/4"NPT Union, d . 'a <br /> 3/4"NPT nipples, DPLLD or PLLD transducer <br /> reducing nipple / Seal-off,epoxy seal per NFPA <br /> t(/ 3"discharge line sec customer supplied) <br /> (customer supplied) (to dispensers) p ( pp ) <br /> / conduit to console <br /> 1 (customer supplied) <br /> DPLLD or PLLD transducer in 2"port <br /> of Big-Flo Leak Detector(customer <br /> �upplied) <br /> Red Jacket Big-Flo 3°x 3"90 degree elbow <br /> Red Jacket Big-Flo Pressurstat kit- (customer supplied) <br /> Pressurstat kit- 2"x 2"x 3"reducing tee P/N 144-314-5 <br /> P/N 144-314-5 and 3"NPT nipple (customer supplied) 3"discharge line(to dispensers) <br /> (customer supplied) (customer supplied) <br /> 12 <br />