Laserfiche WebLink
TEST NO. 1 - SPILL/OVERFILL CONTAINMENT BOXES <br />Pae 1 of 2 <br />Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑ Spill Bucket Manufacturer 0 Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum 0 Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Incon Tester <br />Equipment Resolution: <br />Spill Box #87-1 fill <br />Spill Box #87-1 vap <br />Spill Box #87-2 fill <br />Spill Box #87-2 vap <br />Bucket Diameter: <br />5 gal <br />5 gal <br />5 gal <br />5 gal <br />Bucket Depth: <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: Per Protocol <br />Test Start Time: <br />8:58am <br />10:00am <br />9:17am <br />10:00 <br />Initial Reading (Ri): <br />3.2452 <br />3.9771 <br />3.3460 <br />4.0739 <br />Test End Time: <br />9:13am <br />10:15am <br />9:33am <br />10:15 <br />Final Reading (RF): <br />3.2436 <br />3.9772 <br />3.3424 <br />4.0737 <br />Test Duration: <br />15 min. <br />15 min. <br />16 min. <br />15 min. <br />Change in Reading (RF- <br />RI <br />-,0016 <br />+.0001 <br />-.0036 <br />-.0002 <br />Pass/Fail Threshold or <br />Criteria: <br />3rd Party Certified <br />3`d Party Certified <br />0.002 in. <br />3d Party Certified <br />Test'Resuit 1; <br />CI Pass 0 Fail <br />®. Pass fi 13Farl . <br />P;PAM `Fail <br />®Pass ❑Fail <br />Comments —(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />