Laserfiche WebLink
SANIOAQUIN Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ESCALON MINI MART 1097 YOSEMITE AVE, ESCALON January 11, 2016 <br /> SUMMARY OF VIOLATIONS' <br /> (GLASS 1,CLASS 11,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 201 CCR 2712(b) Failed to maintain alarm logs and/or records of follow up actions. <br /> Maintenance and monitoring records for the last three years were not found on site. The onsite alarm logs didn't <br /> document the following alarms: Dec 11, 2015 (91 STP sump). December 31, 2015 (87 STP sump), and December <br /> 31, 2015 (annular sensor). These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1) date and time of all monitoring or sampling; (2) monitoring equipment calibration and maintenance <br /> records; (3) results of any visual observations; (4) results of sample analysis performed a lab or in the field; (5) logs <br /> of all readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6) results of <br /> inventory readings and reconciliations. Immediately locate and maintain all maintenance and monitoring records for <br /> the last three years on site and submit copies to the EHD. Submit proof of correction to the EHD. <br /> This is a Class II violation. <br /> 209 CCR 2715(c) Designated operator did not inspect all required items and/or the inspection reports not completed. <br /> The designated operator failed to document all the alarms from the attached alarm history on the November 24, <br /> 2015 designated operator monthly inspection report and failed to check that they were responded to appropriately; <br /> the documentation didn't indicate the date of the alarm and only listed that the alarm was for the premium sump. <br /> During the monthly inspection, the designated operator shall review the alarm history for the previous month, check <br /> that each alarm was documented and responded to appropriately, and attach a copy of the alarm history with <br /> documentation taken in response to any alarms to the monthly report. Ensure that designated operators performing <br /> monthly inspections at this facility are including all of the required information on the reports. <br /> This is a Class II violation. <br /> 211 CCR 2715(f)(2) Designated operator employee training not performed or log not kept. <br /> The designated operator employee training log doesn't appear to have been updated, according to Mr. Singh the <br /> training was provided. The designated operator shall train facility employees for which he or she is responsible in <br /> the proper operation and maintenance of the UST system once every 12 months. The training shall include, but is <br /> not limited to: <br /> 1. Operation of the UST system in a manner consistent with the facility's best management practices <br /> 2. Employee's role with regard to monitoring equipment as specified in the facility's monitoring plan <br /> 3. Employee's role with regard to spills and overfills as specified in the facility's response plan <br /> 4. Name of the contact person(s)for emergencies and monitoring equipment alarms <br /> Ensure that employees have been trained by the designated operator, maintain the list on site, and submit a copy of <br /> the training records to the EHD. <br /> This is a Class II violation. <br /> 306 CCR 2630(d) Monitoring equipment is not installed or maintained to detect a leak at the earliest opportunity. <br /> Jumper hoses were observed inside each UDC connecting all the secondary containment spaces of the flexible <br /> product piping. Monitoring equipment shall be maintained to be able to detect a leak at the earliest possible <br /> opportunity. All jumper hoses were disconnected. Ensure that all monitoring equipment is maintained to detect a <br /> leak at the earliest opportunity. This was corrected on site. <br /> This is a repeat violation, Class 11. <br /> FA0000279 PR0231497 SCO01 01/11/2016 <br /> EHD 23-01 Rev.10/31/2017 Page 4 of 6 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-34201 F 209 464-0138 1 www.sjcehd.com <br />