Laserfiche WebLink
ecov/ <br /> Page 4 of 8 <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard ❑Professional Engineer <br /> ❑ Other(Spec) <br /> Test Method Used: ❑Pressure ❑ Vacuum ®Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used: Level Change Indicator Equipment Resolution: 0.0025 <br /> Sump# 1 (87) Sump#2(91) Sump# Sump# <br /> Sump Diameter: 38 in 38 in <br /> Sump Depth: 67 in 62 in <br /> Sump Material: Fiberglass Fiberglass <br /> Height from Tank Top to Top of <br /> Highest Piping Penetration: 8 in 8 in <br /> Height from Tank Top to Lowest <br /> Electrical Penetration: 8 m 9 in <br /> Condition of sump prior to testing: Dry Dry <br /> Portion of Sump Tested' 2"above prod.piping 2"above prod.piping <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ❑Yes❑No®NA ❑Yes[-]No®NA <br /> product and water)?* <br /> Turbine shutdown response time *See comments ' See comments <br /> Is system programmed for fail-safe <br /> ❑Z <br /> shutdown?` es❑No®NA [-]Yes No®NA <br /> P <br /> Was fail-safe verified to be erational? ❑Z es[-]No®NA ❑Yes[:]No®NA <br /> Wait time between applying <br /> pressure/vacuum/water and starting 5 min 5 min <br /> test: <br /> Test Start Time: 10:50 AM 10:55 AM <br /> Initial Reading(R,): 0 0 <br /> Test End Time: 11:20 AM 11:25 AM <br /> Final Reading(RF): 0 0 <br /> Test Duration: 30 min 30 min <br /> Change in Reading(RF-R,): 0 0 <br /> Pass/Fail Threshold or Criteria: 0.0025 0.0025 <br /> Test Result: N Pass; ❑ Fail ED Pass ❑Fail ❑ -Pass ❑ Fail ❑ Pass' ❑Fail <br /> Was sensor removed for testing? ®Yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No[-INA <br /> Was sensor properly replaced and ®yes❑No❑NA ®Yes❑No RNA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> * Sump(s) sensor(s)were tested separately as part of the annual monitor certification test. <br /> ' If the entire depth of the sump is not tested,specify how much was tested. If the answer to as of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />