Laserfiche WebLink
CLOSURE REPORT FOR UNDERGROUND STORAGE TANK 805-DlUl <br /> Any piping closed in place: [ X ]Yes* [ ]No <br /> *(Piping closed in place under concrete slab with generator). <br /> Describe where the piping was closed in place,and how it was closed(e.g.grouted and capped): <br /> Fuel contents were drained into the tank,then the pWing at the edge of the concrete slab was <br /> cut and capped. The 12ii2ing section from the emer1egenerator to where it went into the <br /> concrete pad was also cut and can . Approximately 6-feet of under o d p-ig was left <br /> in-place under the concrete slab. <br /> s <br /> Underground concrete tank anchoring structure(s)were present: [ X ]Yes [ ]No <br /> Size and location of the concrete tank anchoring structure(s): 5-by 7-feet at a death of 9-1/2 feet. <br /> Description of tank and piping condition (corrosion,pitting, holes, etc.): The tank and 12jWne <br /> were in excellent condition. Photographs of the tank were taken by Marion Heaton(6/22/94). <br /> The tank and piping were transported by: Erickson,Inc. <br /> The tank and piping were disposed of as: Non-RCRA Hazardous Waste, Solid (Empty <br /> Containers Last Containing Diesel Fuel with associated in ). Date: 6/22/94 <br /> Name and address of disposal facility: Erickson Inc. (Hauler Registration No. 0019): <br /> 255 Parr Blvd.Richmond,CA 94801 (5 0)235-1393. <br /> [X] Uniform Hazardous Waste Manifest"TSD Facility to Generator"and LLNL Hazardous <br /> Waste Disposal Requisition copies for UST 805-DlU1 are enclosed as Appendix C. <br /> [N/A] UST Disposition Tracking Record enclosed (San Joaquin County Only). <br /> SJC Tank#39-1945-25. <br /> EXCAVATION INFORMATION: <br /> Soil was excavated by: PetroTek. Date: 6/22Z94 <br /> Shoring was required: [ ] Yes [X] No <br /> Type of shoring used: N/A. <br /> Soil types encountered within the tank excavation: <br /> 0-11 ft. Shy clay. <br /> Describe any potential contaminant pathways such as tree roots or underground utility lines <br /> discovered in the excavation: None. <br /> Describe any odors or staining found in the fill material or native soil: None. <br /> Soil Disposal Information: <br /> [ ] Not Applicable. (Soil and backfill placed back into the tank excavation and piping trench). <br /> The volume of disposed soil: N/A cubic yards. <br /> The soil was transported by: N/A <br /> The soil was disposed of as: N/A Date: N/A <br /> The concrete tank anchoring structure(s)was disposed of with the soil: <br /> [ ]Yes* [ ]No I [ ]Left in the Tank Excavation [ ]N/A <br /> *The concrete tank anchoring structure will be disposed of with the soil:however,the method <br /> of disposal has not yet been determined. <br /> If no,describe how the concrete tank anchoring structure(s)was disposed of. N/A <br /> Name and address of disposal facility: Not yet determined,as soil has not yet been disposed of. <br /> Additional native soil removed as part of a remedial effort:[ ]Yes [X]No <br /> [ ] LLNL Hazardous Waste Requisition and Uniform Hazardous Waste Manifest"TSD <br /> Facility to Generator"copy for the soil enclosed. <br /> Volume of native soil removed:. cubic yards. <br /> Volume of backfill removed: 8* cubic yards. *(10 cu.yds.comprised of both soil and backfill) <br /> Describe how the excavated soil was handled (i.e.how and where it was stored): The soil was <br /> stockpiled on,and covered with visqueen,and stored in the B805 area,at Site 300. The soil has <br /> not been disposed of yet. Disposal methods have not yet been determined. <br /> Soil or backfill returned to the tank excavation or piping trench: [ ]Yes [X]No <br /> If yes,volume of soil returned to the excavation: N A cubic yards <br /> Reason for the return of the soil to the tank excavation or piping trench: N/A. <br /> 2 <br />