Laserfiche WebLink
11 <br />n <br />::i11 :•111` �• r - � •- • <br />UNION <br />�/KF <br />Pp' v <br />Boss mount bolts <br />v� WIDTHWISE ADJUSTMENT: +/- 3/8" <br />3/8" Bolts <br />U -Bolt Bracket Not Shown <br />F.1 - When the dispenser is anchored properly, the dispenser inlet or pump inlet should be plumb <br />with the product shear valve. If the product shear valves are positioned correctly, connect them with <br />a union. <br />F.2 - If the valve and inlet are not aligned, determine the distance necessary for the valve to be <br />moved. To adjust the valve lengthwise and/or widthwise, loosen the 3/8" bolts on the bracket ends <br />and on the bracket inserts. Align valve to dispenser inlet and retighten bolts. <br />F.3 - Connect dispenser riser pipe to the product shear valve. A nipple may be required to extend <br />the dispenser riser. <br />For rigid piping apply a UL classified pipe sealant for use and handling <br />of gasoline and petroleum oils to externally threaded connections. <br />F.4 - Now retighten bolts and/or nuts attaching the shear valves to the bracket. Use provided wash- <br />ers. <br />F.5 - Connect electrical and vapor lines to the dispenser as required by local regulations. <br />Always follow electrical and vapor component manufacturers' Installation Instructions. <br />13 ::111 •111 1M <br />