Laserfiche WebLink
SWRCB,Aanuary 2002 Page 3. <br /> 7. UNDER-DISPENSER CONTAINMENT (UD TESTING <br /> Test Method Developed By: F-1 UDC Manufacturer ❑ Industry Standard X❑ Professional Engineer <br /> EJ Other (Specify) <br /> Test Method Used: F] Pressure Vacuum Hydrostatic <br /> 11 Other (Specify) <br /> Test Equipment Used: VPLT Equipment Resolution: <br /> nm��EE UDC# 1/2 UDC# 3/4 UDC# 5/6 UDC# 7/8 <br /> UDC Manufacturer: CS CS CS CS <br /> UDC Material: FIBERGLASS FIBERGLASS FIBERGLASS FIBERGLASS <br /> UDC Depth: 32 IN 32 IN 32 IN 32 IN <br /> Height from UDC Top to Top of 12 IN 12 IN 12 IN 12 IN <br /> Highest Piping Pentration: <br /> Height from UDCTop to Lowest 6 IN 6 IN 6 IN 6 IN <br /> Electrical Pentration: <br /> Condition of UDC prior to testing: GOOD GOOD GOOD GOOD <br /> Portion of UDC Tested: 1 14 IN 14 IN 14 IN 14 IN <br /> Does turbine shut down when <br /> sump sensor detects liquid(both X❑Yes❑No[:]N F]Yes❑No❑N Yes❑No❑N a Yes❑No❑N <br /> product and water)?* <br /> Turbine shutdown response time: 2-5 SEC 2-5 SEC 2-5 SEC 2-5 SEC <br /> Is system programmed for fail-safe ❑ ❑ ❑ ❑ � ❑ � ❑ ❑ �T <br /> shutdown?* X Yes N N X Yes N N X Yes N N X Yes No <br /> Was fail-safe verified to be ❑Yes❑N <br /> X Yes❑N�N X N ❑Yes F]NoONA❑Yes[:]NoaA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and starting 5 MIN 5 MIN 5 MIN 5 MIN <br /> test: <br /> Test Start Time: 9:01 8:58 9:51 9:54 <br /> Initial Reading(Rl): 7.589 4.019 5.007 2.256 <br /> Test End Time: 9:16 9:13 10:06 10:09 <br /> Final Reading(RF): 7.589 4.019 5.007 2.256 <br /> Test Duration: 15 MIN 15 MIN 15 min 15 MIN <br /> Change in Reading(R F-Rl ): 0 0 0 0 <br /> Pass/Fail Threshold or Criteria: .05 GPH .05 GPH .05 GPH .05 GPH <br /> Was sensor removed for testing? X Yes N NA X Yes N NA "__1 Yes N NA x Yes No <br /> Was sensor properly replaced and ❑YeNNA ❑YeC] <br /> N�NA ❑ e�N�NA❑Yes❑ <br /> N <br /> verified functional after testing <br /> Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 1 If the entire depth of the UDC is not tested,specify how much was tested.If the answer to a_kof the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />