Laserfiche WebLink
SWRCB January 2002 Pate 3 of i <br /> 7. UNDER-DISPENSER CONTAINMENT UDC TESTING <br /> Test Method Developed By: ❑UDC Manufacturer ❑Industry Standard ❑Professional Engineer <br /> X Other(Spec) Incon <br /> Test Method Used: ❑Pressure ❑Vacuum X Hydrostatic <br /> Other(Spec) <br /> Test Equipment Used: Incon TS-STS Sump Test System Equipment Resolution: 0.002 <br /> UDC# 1/2 UDC#3/4 UDC#5/6 UDC#7/8 <br /> UDC7Depth: <br /> Bravo Bravo Bravo Bravo <br /> UDC Steel Steel Steel Steel <br /> UDC 12" 12" 12" 12" <br /> Height from UDC Bottom to Top 1" 1" 1" 1" <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Dirty Dirty Dirty Dirty <br /> testing: <br /> Portion of UDC Tested' 1/3 1/3 1/3 1/3 <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ❑Yes ❑No X NA ❑Yes ❑No X NA ❑Yes ❑No X NA ❑Yes ❑No X NA <br /> product and water)?* <br /> Turbine shutdown response time N/A N/A N/A N/A <br /> Is system programmed for fail- ❑Yes ❑No X NA ❑Yes ❑No X NA ❑Yes ❑No X NA ❑Yes ❑No X NA <br /> safe shutdown?* <br /> Was fail-safe verified to be ❑Yes ❑No X NA ❑Yes ❑No X NA ❑Yes ❑No X NA ❑Yes ❑No X NA <br /> operational?* <br /> Wait time between applying 5 min 5 min 5 min 5 min <br /> pressure/vacuum/water and <br /> starting test <br /> Test Start Time: 3:20 3:20 3:20 3:45 <br /> Initial Reading(RI): 0.1600 0.2045 0.9919 0.5017 <br /> Test End Time: 3:35 3:35 3:35 4:01 <br /> Final Reading(RF): 0.1598 0.2037 0.9915 0.4999 <br /> Test Duration: 15 min 15 min 15 min 15 min <br /> Change in Reading(RF-RI): 0.0002 0.0008 0.0004 0.0018 <br /> Pass/Fail Threshold or Criteria: 0.002 0.002 0.002 0.002 <br /> Was sensor removed for testing. ❑ Yes ❑No X NA ❑ Yes ❑No X NA ❑ Yes ❑No X NA ❑ Yes ❑No X NA <br /> Was sensor properly replaced and ❑ Yes ❑No X NA ❑ Yes ❑No X NA ❑ Yes ❑No X NA ❑ Yes ❑No X NA <br /> verified functional after testing? <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> MAR <br /> ENVIRONMENITAi <br /> 'If the entire depth of the UDC is not tested,specify how much was tested. If the answer to pgy of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRC13 LG-160) <br />