Laserfiche WebLink
Page 6 of 9 O/C <br /> 8. UNDER-DISPENSER CONTAINMENT UDC TESTING <br /> Test Method Developed By: ❑UDC Manufacturer El Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ❑ Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Equipment Resolution: <br /> UDC# 9/10 UDC# 11/12 UDC # UDC# <br /> UDC Manufacturer: U.K U.K <br /> UDC Material: FG FG <br /> UDC Depth: 30" 30" <br /> Height from UDC Bottom to Top of 12" 12" <br /> Highest Piping Penetration: <br /> Height from UDC Bottom to Lowest 4" 4" <br /> Electrical Penetration: <br /> Condition of UDC prior to testing: Dry Dry <br /> Portion of UDC Tested' 16" 16" <br /> Does turbine shut down when UDC <br /> sensor detects liquid(both product ❑ Yes ❑ No ® NA ❑ Yes ❑ No IHI NA ❑Yes ❑ No ❑ NA ❑Yes ❑ No ❑ NA <br /> and water)?* <br /> Turbine shutdown response time N/A N/A <br /> Is system programmed for fail-safe ❑ Yes ❑ No RI NA ❑ Yes ❑ No ® NA ❑Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> shutdown?' <br /> Was fail-safe verified to be ❑ Yes ❑ No ® NA ❑ Yes ❑ No ® NA ❑ Yes ❑ No ❑ NA ❑Yes ❑ No ❑ NA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and starting 0 0 <br /> test <br /> Test Start Time: 4:30 pm 4:30 pm <br /> Initial Reading Ri : 15 1/2- 15" <br /> Test End Time: 5:30 pm 5:30 pm <br /> Final Reading(RF): 15 1/2" 15" <br /> Test Duration: lhr lhr <br /> Change in Reading RF-Ri : 0 0 <br /> Pass/Fail Threshold or Criteria: 0 0 <br /> Test Result: 91 Pass ❑ Fail [R) Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass LJ Fail <br /> Was sensor removed for testing? ® Yes ❑ No ❑ NA ® Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑Yes ❑ No ❑ NA <br /> Was sensor properly replaced after ® Yes ❑ No ❑ NA ® Yes ❑ No ❑ NA ❑Yes ❑ No ❑ NA ❑Yes ❑ No ❑ NA <br /> testing? <br /> Comments—(include information on repairs made prior to testing,and recommended follow-up for failed tests) <br /> 'If the entire depth of the UDC is not tested,specify how much was tested. If the answer to ggy of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />