16: Tanks subject to floatation. (Section 2635 (a) (7)] <br /> A. Anchored by deadman or stab. <br /> 8. Anchors to be installed as specified by manufacturer. <br /> C. Installation details provided on plans. <br /> 0. Calculations provided. <br /> 17. SPILL AND OVERFILL PREVENTION <br /> Underground storage tank equipped with spill container and an overfill prevention system. (detail drawing of spill <br /> containers)/piping sump(s) required, including tank fill and all openings). <br /> A. Spill container [Section 2635 (b) (1)l. <br /> 1 If made of metal, exterior wall protected from galvanic corrosion. <br /> Capacity: (minimum of five gallons) <br /> Equipped with a drain valve which allows drainage of spill into primary container. <br /> r Manufacturer- <br /> ✓ B. Overfill prevention system does not allow for manual override and meets one of the following requirements: <br /> (1) Atert transfer operator at 90% full by restricting the flow into the tank or triggering an audibte <br /> and visual alarm [Section 2635(b)(2)(A)l . <br /> Manufacturer• Model: <br /> _ (2) Restrict delivery flow to the tank 30 minutes before overfill when tank is filled at no more than <br /> 95% capacity and activates an audible alarm at least five minutes before overfill [Section 2635 <br /> (b) (2) (B)l. <br /> Manufacturer- Model:_ <br /> (3) Provide positive shut off at no more than 95% capacity [Section 2635 (b) (2) (C)l. <br /> Manufacturer- Model: <br /> (4) Provide positive shut-off of flow to the tank so that the fittings on top of the tank are not <br /> exposed to the product overfilling CSection 2635 (b) (2) MI. <br /> Manufacturer- :Model: 6z'-wo <br /> 18. PIPING INFORMATION <br /> PIPING INFORMATION TANK# TANKS TANKA TANK$ <br /> DISTANCE from f <br /> DISPENSER to TANK 1 <br /> MANUFACTURER ke, ,SwJ <br /> SYSTEM TYPE <br /> CONSTRUCTION ** <br /> MATERIAL *** <br /> LEAK DETECTION SYSTEM <br /> 100% METHANOL COMPATIBILITY YES NO <br /> CORROSION PROTECTION AYES NO <br /> ' System Type; suction, pressure, and gravity <br /> "* Construction: single-wafted, double-walled, lined-trench, etc. <br /> **� Material Type; steel with cathodic protection, stainless-steel, fiberglass reinforced plastic- <br /> 7 <br />