FEB -25-2011 15:49 Service Station Systems 408 938 8888 P.08 <br />Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: ❑ Spill BucketManufacturer ® Industry Standard ❑ Professional Engineer <br />I❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum M Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Incon Sump Tester <br />Fill Spill Box # 87 Fill Spill Sox # 89 <br />Equipment Resolution: +/-0.002" <br />Fill Spill Box # 91 <br />Diameter: 12" 12" <br />12" <br />Bucket Depth. 10" 10" <br />Bucket <br />101, <br />Wait time between applying <br />pressure/vacuum/water and 10 min. 10 min. <br />starting test: <br />10 min. <br />Test Start Time: 8:07 am 8:07 am <br />8:07 am <br />Initial Reading (RI): <br />6.0203 5.0938 <br />6.2601 <br />Test End Time: <br />8:22 am 8:22 am <br />8:22 am <br />Final Reading (RF): <br />6.0204 5.0936 <br />6.2602 <br />Test Duration: <br />15 min. 15 min. <br />15 min. <br />Change in Reading (R, -Rt): <br />-1-0.0001 -0.0002 <br />+0.0001 <br />Pass/rail Threshold or <br />Criteria: <br />+/-0.002" +/-0,002" <br />+/-0.002" <br />Test Result: <br />® Pass ❑ Fail ® .Pass ❑ Fall <br />® Pass ❑ Fail <br />Comments — (include information on repairs made prior to testing, and recommenced fellow-up.for,failed tests) - <br />