Page 5 of 6 <br />7. UNDER -DISPENSER CONTAINMENT (UDC) TESTING <br />Test Method Developed By: <br />❑ UDC Manufacturer <br />❑ Other (Specify) <br />X lry swwad ❑ Professional Engineer <br />Test Method Used: <br />❑ Pressure <br />❑ Other (Specify) <br />❑ Vacuum X Hydrcetwc <br />Test Equipment Used: INCON TS -STS V2.1 <br />- UDC # RLsp 01 UDC # <br />UDC Manufacturer: Total Containment <br />Equipment Resolution: 0.0000" <br />UDC # UDC # <br />UDC Material: <br />Plastic <br />UDC Depth: <br />24" <br />Height from UDC Bottom to Top <br />of Highest Piping Penetration: <br />6" <br />Height from UDC Bottom to <br />Lowest Electrical Penetration: <br />4" <br />Condition of UDC prior to <br />testing: <br />Clean <br />Portion of UDC Tested <br />None <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />product and water)?* <br />X Yes ❑ No ❑ NA <br />Turbine shutdown response time <br />4 Seconds <br />Is system programmed mmed for fail- <br />safe shutdown? <br />X Yes ❑ No ❑ NA <br />Was fail-safe verified to be <br />o rational?' <br />X Yes ❑ No ❑ NA <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test <br />Test Start Time: <br />Visual Fail <br />Initial Reading (RI): <br />Test Erni Time. <br />Final Reading (RF): <br />Test Duration: <br />Change in Reading (RF-Rq): <br />Pass/Fad Threshold or Criteria: <br />0.0020" <br />Test Result: <br />❑ Pass X to <br />Was sensor removed for testing? <br />X Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testin ? <br />X Yes ❑ No ❑ NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up far failed tests) <br />_Dish 01 Electrical penetration on west side of under dispenser containment <br />box is torn. <br />All Hydrostatic Test Performed Twice To Ensure Testinp, Results. <br />' If the entire depth of the UDC is not tested, specify how much was tested If the answer to M of the questions indicated with an <br />asterisk(*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />