Laserfiche WebLink
7SWRCB, January 2002 <br />8. FILL RISER CONTAINMENT SUMP TESTING <br />Page 6 of 7 <br />Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br />Fill Riser Containment Sumps are Present, but were Not Tested ❑ <br />Test Method Developed By: <br />❑ Sump Manufacturer <br />❑ Other (Specify) <br />® Industry Standard ❑ Professional Engineer <br />Test Method Used: <br />❑ Pressure <br />❑ Other (Specify) <br />❑ Vacuum ® Hydrostatic <br />Test Equipment Used: INCON STS <br />Fill Sump # 1 <br />Equipment Resolution:.002 <br />Fill Sump # Fill Sump # <br />Fill Sump # <br />rSumpameter: <br />37" <br />epth: <br />48" <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />18" <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />20" <br />Condition of sump prior to testing: <br />Good <br />Portion of Sump Tested <br />2" Above piping <br />Penetration <br />Sump Material: <br />Fiberglass <br />Wait time between applying <br />pressure/vacuum/water and starting <br />test: <br />15 Minutes <br />Test Start Time: <br />10:58/11:13 <br />Initial Reading Ri): <br />3.2847/3.2838 <br />Test End Time: <br />11:13/11:28 <br />Final Reading (RF): <br />3.2839/3.2837 <br />Test Duration: <br />2-15 Minute Tests <br />Change in Reading RF-Ri): <br />.0008/.0001 <br />Pass/Fail Threshold or Criteria: <br />.002/.002 <br />Test Result: <br />N Pass ❑ Fail <br />❑ Pass ❑ Fail ❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Is there a sensor in the sump? <br />® Yes ❑ No <br />❑ Yes ❑ No ❑ Yes ❑ No <br />❑ Yes ❑ No <br />Does the sensor alarm when either <br />or water is detected? <br />❑ Yes ❑ No ® NA <br />❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />-product <br />Was sensor removed for testing? <br />® Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />® Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />