Laserfiche WebLink
03/18/2015 02:13PM 6616349233 KERN CONSTRUCTION PAGE 18/27 <br /> SWRCB,January 2002 Page 5- of <br /> 7. UNDER-DISPENSER CONTAINMENT UDC TESTING <br /> Test Method Developed By: ❑UDC Manufacturer x Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum x Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used:lncon is-sts Equipment Resolution:.001" <br /> UDC#7 Sat UDC#3-4 UDC#5-6 Sat UDC#6-7 <br /> UDC Manufacturer: Bravo <br /> UDC Material: Steel <br /> UDC Depth: 12" <br /> Height from UDC Bottom to Top 0" <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 0" <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to Clean <br /> testing: <br /> Portion of UDC Tested' 1/2 <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ❑Yes ❑No X NA ❑Yes ❑No ❑NA ❑Yes ❑No DNA ❑Yes ❑No ❑NA <br /> product and water)?* <br /> Turbine shutdown response time <br /> j Is system programmed for fail- <br /> safe shutdown?` ❑yes ❑No X NA ❑Yes ❑No ❑NA 0 Yes ❑No ❑NA ❑Yes ❑No DNA <br /> Was fail-safe verified to be ❑yes ❑No X NA ❑Yes D No DNA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> operational?* <br /> Wait time between applying 15 min. <br /> pressure/vacuum/water and <br /> starting test <br /> Test Start Time: 9:15 <br /> Initial Reading(Ri): 0.620 <br /> Test End Time: 9:30 <br /> Final Reading(RF): 0.619 <br /> Test Duration: 15 Min <br /> Change in Reading(RF-RI): 0.001 <br /> Pass/Fail Threshold or Criteria: 0.002 <br /> Test:Result: X..Pass .0 Fail ❑ Pass ❑Fail D;Pass .d Fail_': i1.Pass`°:.OFgil <br /> Was sensor removed for testing? 0 Yes ❑No X NA ❑Yes ONO DNA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> Was sensor properly replaced and ❑Yes ❑No X NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes D No ❑NA <br /> verified functional after testing? 11 <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> MAR 19 2015 <br /> ENVIRONMI Tei <br /> !Jr'� T►.7 <br /> 05 -r <br /> 'If the entire depth of the UDC is not tested,specify how much was tested. If the answer to my of the questions indicated with an <br /> asterisk(*)is`NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br /> Received Time Mar. 18, 2015 3: 16PM No. 8366 <br />