My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2009-2011
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
J
>
JACK TONE
>
1501
>
2300 - Underground Storage Tank Program
>
PR0505264
>
COMPLIANCE INFO_2009-2011
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
7/28/2021 3:56:53 PM
Creation date
6/23/2020 6:57:06 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2009-2011
RECORD_ID
PR0505264
PE
2361
FACILITY_ID
FA0006672
FACILITY_NAME
FLYING J TRAVEL PLAZA #618*
STREET_NUMBER
1501
Direction
N
STREET_NAME
JACK TONE
STREET_TYPE
RD
City
RIPON
Zip
95366
APN
22811017
CURRENT_STATUS
01
SITE_LOCATION
1501 N JACK TONE RD
P_LOCATION
05
P_DISTRICT
004
QC Status
Approved
Scanner
SJGOV\rtan
Supplemental fields
FilePath
\MIGRATIONS\UST\UST_2361_PR0505264_1501 N JACK TONE_2009-2011.tif
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
394
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
SWRCB, January 2002 <br />C <br />7. UNDER -DISPENSER CONTAINMENT <br />C <br />TESTING <br />Page 5 of 7 <br />Test Method Developed By: ❑ UDC Manufacturer M Industry Standard U Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ® Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used:Incon TS -STS Equipment Resolution: +/-0. 000 1" <br />rDCUDCManufacturer:Material: <br />UDC #9-10 <br />UDC #11-12 <br />UDC #13 <br />UDC #14-15 <br />FRP <br />FRP <br />FRP <br />FRP <br />Depth: <br />30" <br />30" <br />30" <br />30" <br />Height from UDC Bottom to Top <br />of Highest Piping Penetration: <br />811 <br />8" <br />11" <br />11" <br />Height from UDC Bottom to <br />Lowest Electrical Penetration: <br />7" <br />4" <br />N/A <br />N/A <br />Condition of UDC prior to <br />testing: <br />Clean <br />Clean <br />Clean <br />Clean <br />Portion of UDC Tested <br />2"above highest Pipe pen <br />2"above highest Pipe pen <br />2"above highest Pipe pen <br />2"above highest Pipe pen <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />and water)?* <br />®Yes ❑No DNA <br />®Yes [:]No DNA <br />®Yes ❑No DNA <br />®Yes [:]No DNA <br />-product <br />Turbine shutdown response time <br />Is system programmed for fail- <br />safe shutdown?* <br />®yes [-]No DNA <br />®Yes ❑No DNA <br />®Yes ❑No ❑NA <br />®Yes ❑No DNA <br />Was fail-safe verified to be <br />[-]Yes [-]No NA <br />® <br />❑Yes No NA <br />❑ ® <br />❑Yes No <br />❑ ®NA <br />❑Yes ❑No ®NA <br />-operational?* <br />Wait time between applying <br />pressure/vacuum/water and <br />test <br />15 Minutes <br />15 Minutes <br />15 Minutes <br />15 Minutes <br />-starting <br />Test Start Time: <br />9:29 9:45 <br />9:29 9:45 <br />11:13 11:30 <br />10:40 10:57 <br />Initial Reading (Rt): <br />5.5431 5.5425 <br />4.4153 4.4148 <br />4.1818 4.1808 <br />3.6950 3.6951 <br />Test End Time: <br />9:44 10:00 <br />9:44 10:00 <br />11:28 11:45 <br />10:55 11:12 <br />Final Reading (RF): <br />5.5426 5.5424 <br />4.4148 4.4138 <br />4.1811 4.1791 <br />3.6953 3.6940 <br />Test Duration: <br />15 Min Each (30 Min) <br />15 Min Each (30 Min) <br />15 Min Each (30 Min) <br />15 Min Each (30 Min) <br />Change in Reading (RF -RI): <br />0.0005 1 0.0001 <br />0.0005 1 0.0013 <br />0.0007 1 0.0017 <br />0.0003 1 0.0011 <br />Pass/Fail Threshold or Criteria: <br />+/- 0.002" <br />+/- 0.002" <br />+/- 0.002" <br />+/- 0.002" <br />Test Result: ; <br />® Pass - ❑ Fail <br />0 Pass ; ❑ Fail <br />® Pass ❑ Fail ` <br />® Pass " ❑ Fail ; <br />Was sensor removed for testing? <br />®Yes ❑No DNA <br />®Yes ❑No [:INA <br />®Yes [:]No ❑NA <br />®Yes [:]No DNA <br />Was sensor properly replaced and <br />verified functional after testing? <br />®Yes ❑No DNA <br />®Yes [-]No DNA <br />®Yes [:]No ❑NA <br />®Yes [-]No DNA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Dispenser #9-10,11-12,13 and 14-15 all passed hydrotatic test. <br />t If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or `NA", the entire UDC must be tested. (See SWRCB LG -160) <br />
The URL can be used to link to this page
Your browser does not support the video tag.