Laserfiche WebLink
SWRCB,January 2002 0 Page 11 <br /> 7. UNDER-DISPENSER CONTAINMENT (UDC) TESTING <br /> Test Method Developed By: ❑ UDC Manufacturer FlIndustry Standard ❑X Professional Engineer <br /> D Other (Specify) <br /> Test Method Used: F] Pressure F-1 Vacuum Hydrostatic <br /> E] Other (Specify) <br /> Test Equipment Used: vpl t Equipment Resolution: vplt to gph <br /> MEN= UDC# 1/2 UDC# 3/4 UDC# 5/6 UDC# 7/8 <br /> UDC Manufacturer: W.f. W.f. W.f. W.f. . <br /> UDC Material: fiberglass fiberglass fiberglass fiberglass <br /> UDC Depth: 3111 3111 3111 311t <br /> Height from UDC Top to Top of 91, 9" 91, 9" <br /> Highest Piping Pentration: <br /> Height from UDCTop to Lowest 1/211 1/2" 1/211 1/2" <br /> Electrical Pentration: <br /> Condition of UDC prior to testing: good good good good <br /> Portion of UDC Tested: 1 1111 11" <br /> Does turbine shut down when <br /> sump sensor detects liquid(bothX❑yes❑No❑N Yes F]No[:]NA MYes❑No❑N E Yes[:]No[:]N <br /> product and water)?* <br /> Turbine shutdown response time: 2-5sec 2-5sec 2-5sec 2-5 s e c <br /> Is system programmed for fail-safe ❑ ❑ � __7 <br /> ❑ � ❑ --]No[7]NA <br /> ❑ ❑ <br /> shutdown?* X Yes N N X Yes N N X Yes N N X Yes No <br /> Was fail-safe verified to be ❑ � ❑ � ❑ � ❑ DN <br /> operational?* X Yes N N X❑Yes N N X Yes N N X Yes No <br /> Wait time between applying <br /> pressure/vacuum/water and starting 5MIN 5MIN 5MIN 5MIN <br /> test: <br /> Test Start Time: 17:07 16:32 16:2 6 16:05 <br /> Initial Reading(Rt): 6.920 3.856 2.862 2 .134 <br /> Test End Time: 17:22 16:4 7 16:31 16:2 0 <br /> Final Reading(RF): 6.920 3 .856 2 .862 2.134 <br /> Test Duration: 15min 15min 15min 15min <br /> Change in Reading(RF-Rt ): .o0ogph .000gph .000gph .000gph <br /> Pass/Fail Threshold or Criteria: .05gph .05gph .05gph .05gph <br /> Was sensor removed for testing? �Yes�No❑NA X Yes❑No❑NA Yes❑NoE]NA Yes❑No[]N <br /> Was sensor properly replaced and s0 � ❑ <br /> verified functional after testing? X❑Ye�N ❑NA X Ye�N� X NA Ye N NA X yes❑N <br /> Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 1 If the entire depth of the UDC is not tested,specify how much was tested.If the answer to aof the questions indicated with an <br /> asterisk(*)is "NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />