SWRCB, January 2002 <br />8. <br />Page of <br />FILL RISER CONTAINMENT SUMP TESTING <br />Facility is Not Equipped With Fill Riser Containment Sums ❑ <br />Fill Riser Containment Sumps are Present, but were Not Tested ❑ <br />Test Method Developed By: <br />❑ Sump Manufacturer <br />❑ Other (Spec) <br />® Industry Standard ❑ Professional Engineer <br />Test Method Used: <br />X Pressure <br />❑ Other (Spec) <br />❑ Vacuum <br />❑ Hydrostatic <br />Test Equipment Used: Incon <br />Incon TS -STS Tester <br />Equipment Resolution: +/-0.002" <br />NEENEEMFill <br />Sump Diameter: <br />Sump # 87 <br />36" <br />Fill Sump # 87 <br />36" <br />Fill Sump # 87 <br />36" <br />Fill Sump # 87 <br />36" <br />Sump Depth: <br />60" <br />60" <br />60" <br />60" <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />15" <br />17" <br />15" <br />16" <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />30" <br />30" <br />32" <br />31" <br />Condition of sump prior to <br />testing: <br />Dry <br />Dry <br />Dry <br />Dry <br />Portion of Sump Tested <br />34" <br />35" <br />36" <br />35" <br />Sump Material: <br />Fiberglass <br />Fiber lass <br />Fiberglass <br />Fiber lass <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />15 minutes <br />15 minutes <br />15 minutes <br />15 minutes <br />Test Start Time: <br />9:16am 9:36am <br />9:16am 9:36am <br />10:11 am 10:28am <br />10:11 am 10:28am <br />Initial Reading RI): <br />4.7621" 4.7618" <br />4.3756" 4.3751" <br />5.5485" 5.5487" <br />4.0976" 4.0970" <br />Test End Time: <br />9:31 am 9:51 am <br />9:31 am 9:51 am <br />10:26am 10:43am <br />1 <br />10:26am 10:43am <br />Final Reading (RF): <br />4.7617" 4.7615" <br />4.3752" 4.3751" <br />5.5482" 5.5488" <br />4.0972" 4.0959" <br />Test Duration: <br />15 Minutes Each 30 <br />15 Minutes Each 30 15 Minutes Each 30 <br />15 Minutes Each 3 <br />Chane in Reading (RF -RI): <br />-0.0004 1 -0.0003 <br />-0.0004 <br />0.0000 <br />-0.0003 0.0001 <br />-0.0004 -0.0011 <br />Pass/Fail Threshold or Criteria: <br />+/-0.002" +/-0.002" <br />+/-0.002" <br />+/-0.002 +/-0.002" +/-0.002 <br />+/-0.002" +/-0.002 <br />Test Result: <br />9 Pass D Fail <br />® Pass ©`Fail <br />® Pass ❑ Fail <br />® Pass d Fail <br />Is there a sensor in the sump? <br />d Yes ❑ No <br />L Yes ❑ No <br />9 Yes ❑ No <br />® Yes ❑ No <br />Does the sensor alarm when <br />either product or water is <br />detected? <br />ie Yes ❑No ❑ NA <br />U Yes ❑ No ❑ NA <br />9 Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />Was sensor removed for testing? <br />® Yes ❑No ❑ NA <br />9 Yes ❑ No ❑ NA <br />®Yes ❑ No ❑ NA <br />®Yes []No ❑NA <br />Was sensor properly replaced and k yes ❑No ❑ NA <br />verified functional after testin ? <br />I X Yes ❑ No [INA <br />®Yes ❑ No ❑ NA <br />®Yes []No ❑ NA <br />Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />