n <br />1. Make with symmetrical bends or cast metal fittings. <br />2. Bends and offsets shall be made with a hickey or conduit bending machine. <br />F. Supports: <br />1. Provide pipe straps, wall brackets, conduit clamps, conduit hangers, threaded <br />C -clamps with retainers, or ceiling trapeze. <br />2. Securely and rigidly fasten in place. <br />3. Maximum Interval: 10 feet. <br />3.04 CONDUCTORS <br />A. Conduit system shall be complete prior to drawing conductors. <br />B. Lubricate prior to drawing into conduit. Lubrication type shall be as approved by <br />conductor manufacturer. <br />C. Connections: Pressure type solderless, complete with insulator and security ring. <br />D. Control Circuits: <br />1. Where multiple units perform parallel operations, do not group all devices on <br />same branch circuit. <br />2. Do not exceed the ampacity of the branch circuit, or 12 amperes continuous. <br />3. Terminate feeder and interconnecting conductors between panel mounted <br />equipment and external equipment at numbered terminal blocks. <br />4. Keep adequate separation between power and signal cables. <br />E. Identification: <br />1. Where two or more conduits run to a single outlet box, color code each circuit <br />as a guide in making connections. <br />2. Carry colors continuously throughout the system if more than one multi -wire <br />branch circuit is carried through a single raceway. <br />3. Connect circuit conductors of same color to same underground feeder <br />conductor throughout installation. <br />4. Colors: <br />a. Neutral Wire: White. <br />b. Live Wire, 120/240 -Volt System: Black, red, .or blue. <br />C. Live Wire, 277/480 -Volt System: Brown, orange, or yellow. <br />d. Ground Wire: Green. <br />3.05 TERMINAL BLOCKS <br />A. All control circuits leaving or entering equipment, panels, or boxes shall be through <br />terminal blocks. <br />North County LFG Collection System 17 FLARE STATION ELECTRICAL <br />San Joaquin County Public Works Section 16005 <br />