Laserfiche WebLink
SAN <br /> Q U IN Environmental Health Department <br /> COUNTY <br /> RCRA Large Quantity Hazardous Waste Generator Inspection Report <br /> Facility Name: Facility Address: Date: <br /> OWENS-BROCKWAY GLASS CONTAINER INC 1 14700 W SCHULTE RD TRACY June 05 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 502 CCR 66265.192(a) Failed to comply with new hazardous waste tank system assessment requirements. <br /> Facility does not have a tank assessment for the 1,550-gallon oily water tank. <br /> The owner or operator of a hazardous waste tank shall obtain a written assessment reviewed and certified by an <br /> independent, qualified, professional engineer, registered in California attesting that the system has sufficient structural <br /> integrity, is acceptable for the transferring, storing, and treating of hazardous waste, and that the tanks and <br /> containment system are suitably designed. <br /> Immediately have an assessment prepared for the 1,550-gallon oily water tank. <br /> Submit a schedule showing when this will be accomplished to the EHD. <br /> This is a Class I violation. <br /> FA0006674 PR0220086 SCO01 06/05/2019 <br /> EHD 22-03 Rev.09/27/2018 Page 10 of 13 RCRA Large Quantity Hazardous Waste Generator OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />