Laserfiche WebLink
SWRCB , January 2002 <br /> 6. PIPING SUMP TESTING <br /> Test Method Developed By : ❑ Sump Manufacturer ❑X Industry Standard ❑ Professional Engineer <br /> ❑ Other (Spec) <br /> Test Method Used : ❑ Pressure ❑ Vacuum XO Hydrostatic <br /> ❑ Other (Spec) <br /> Test Equipment Used : INCON TS-STS Equipment Resolution : 0. 0006 <br /> UE0580002 <br /> Sump Diameter: 38" <br /> Sump Depth : 42" <br /> Sump Material : Fiberglass <br /> Height from Tank Top to Top of 22 " <br /> Highest Piping Penetration : <br /> Height from Tank Top to Lowest 21 „ <br /> Electrical Penetration : <br /> Condition of sump prior to testing : Gdood <br /> Portion of Sump Tested ' 2" above high pen . <br /> Does turbine shut down when <br /> sump sensor detects liquid (both ❑1' es ❑No SNA ❑Yes ❑No ❑ NA ❑Yes ❑No <br /> ❑NA ❑ Yes ❑No ❑NA <br /> product and water)? * <br /> Turbine shutdown response time N/A <br /> Is system programmed for fail-safe DYes ❑No FX'JNA <br /> ❑ <br /> shutdown?` Yes ❑No ❑ NA ❑Yes ❑No ❑NA ❑ Yes ❑ No ❑NA <br /> Was fail-safe verified to be ❑Yes ❑ No [KNA <br /> operational?' ❑Yes ❑No ❑ NA ❑Yes ❑No ❑NA ❑ Yes ❑No ❑ NA <br /> Wait time between applying <br /> pressure/vacuum/water and starting 15 minutes <br /> test: <br /> Test Start Time : 9: 32am 9 : 47am <br /> Initial Reading (Rj) : 1 . 7317 1 . 7312 <br /> Test End Time : 9 : 47am 10: 02am <br /> Final Reading (Rr) : 1 . 7313 1 . 7311 <br /> Test Duration : 15 minutes 15 minutes <br /> Change in Reading (Rr-Rj) : 0. 0004 0. 0001 <br /> Pass/Fail Threshold or Criteria: 002 . 002 <br /> Test Result : El Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑Fail ❑ Pass DFail <br /> Was sensor removed for testing? [Z]Yes ❑No ❑ NA ❑Yes No NA Yes No NA <br /> ❑ ❑ ❑ ❑ ❑ ❑ Yes [:]No ❑NA <br /> Was sensor properly replaced and ❑Yes ❑X No ❑NA <br /> verified functional after testing? ❑Yes ❑No ❑ NA ❑Yes ❑No ❑NA Dyes ❑ No ❑NA <br /> Comments — (include information on repairs made prior to testing, and f•ecomtnended follow-up for failed tests) <br /> The sensor was reinstalled to the lowest point, but not tested . <br /> ' If the entire depth of the sump is not tested, specify how much was tested . If the answer to aM of the questions indicated with an <br /> asterisk ( * ) is "NO" or "NA ", the entire sump must be tested . (See SWRCB LG- 160) <br />