Laserfiche WebLink
SAN J 0 A Q I I I Irl Environmental Health Department <br /> CCUN r <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ESCALON UNIFIED SCHOOL DIST 1 1176 STANISLAUS ST, ESCALON August 06, 2021 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 711 CFR 112.8(c)(6)Plan failed to adequately discuss procedures to test or inspect each container for integrity. <br /> OBSERVATION: The Spill Prevention, Control, and Countermeasure(SPCC)Plan does not adequately discuss <br /> procedures to test or inspect each aboveground container for integrity in accordance with industry standards. The <br /> referenced industry standard, STI SP001,frequency of formal inspections is not mentioned in the SPCC plan. <br /> REGULATION GUIDANCE: (c)(6)Test or inspect each aboveground container for integrity on a regular schedule <br /> and whenever you make material repairs. You must determine, in accordance with industry standards,the <br /> appropriate qualifications for personnel performing tests and inspections, the frequency and type of testing and <br /> inspections,which take into account container size, configuration, and design (such as containers that are: <br /> shop-built,field-erected, skid-mounted, elevated, equipped with a liner, double-walled, or partially buried). Examples <br /> of these integrity tests include, but are not limited to:visual inspection, hydrostatic testing, radiographic testing, <br /> ultrasonic testing, acoustic emissions testing, or other systems of non-destructive testing.You must keep <br /> comparison records, and you must also inspect the container's supports and foundations. In addition,you must <br /> frequently inspect the outside of the container for signs of deterioration,discharges, or accumulation of oil inside <br /> diked areas. Records of inspections and tests kept under usual and customary business practices satisfy the record <br /> keeping requirements of this paragraph. <br /> CORRECTIVE ACTION: Ensure that the SPCC Plan adequately discusses facility's procedures to test and inspect <br /> aboveground/bulk storage containers in accordance with all applicable industry standards. This discussion must <br /> include, but not be limited to, inspection/testing schedule/frequency, and personnel qualifications. Submit proof of <br /> correction to the EHD. <br /> This is a repeat violation, Class II. <br /> 715 CFR 112.8(c)(8), 25270.4.5(a)Failed to have a high level monitoring and to engineer or update containers to avoid <br /> discharge. <br /> OBSERVATION: The SPCC plan states that all tanks are equipped with with direct reading level gauges and high <br /> level alarms. Only the 10,000 gallon diesel tank was observed with a direct reading level guage and high level <br /> alarm. The gasoline, used oil,transmission oil and motor oil tanks were observed with only direct reading level <br /> gauges. <br /> REGULATION GUIDANCE: (c)(8)Engineer or update each container installation in accordance with good <br /> engineering practice to avoid discharges.You must provide at least one of the following devices: <br /> (i) High liquid level alarms with an audible or visual signal at a constantly attended operation or surveillance station. <br /> In smaller facilities, an audible air vent may suffice. <br /> (ii)High liquid level pump cutoff devices set to stop the flow at a predetermined container content level. <br /> (iii)Direct audible or code signal communication between the container gauger and the pumping station. <br /> (iv)A fast response system for determining the liquid level of each bulk storage container such as digital computers, <br /> telepulse, or direct vision gauges. If you use this alternative, a person must be present to monitor gauges and the <br /> overall filling of bulk storage containers. <br /> CORRECTIVE ACTION: Ensure the SPCC plan accurately describes the high liquid level monitoring devices for <br /> each tank and provide proof of correction to the EHD. <br /> This is a repeat violation, Class II. <br /> FA0003822 PR0528253 SCO01 08/06/2021 <br /> EHD 28-01 Rev.9/16/2020 Page 9 of 11 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />