1.1MATERIALSA.CONDUCTORS AND CABLES:1.CONDUCTORS: COPPER.2.CONDUCTOR INSULATION: TYPE THHN/THWN-2, TYPE XHHW-2, TYPE USE ANDTYPE SO.3.MULTICONDUCTOR CABLE: METAL-CLAD CABLE, TYPE MC WITH GROUND WIRE.1.2CONDUCTOR MATERIAL APPLICATIONSA.FEEDERS: COPPER. SOLID FOR NO. 10 AWG AND SMALLER; STRANDED FOR NO. 8 AWGAND LARGER.B.BRANCH CIRCUITS: COPPER. SOLID FOR NO. 12 AWG AND SMALLER; STRANDED FORNO. 10 AWG AND LARGER, EXCEPT VFC CABLE, WHICH SHALL BE EXTRA FLEXIBLESTRANDED.1.3CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND WIRINGMETHODSA.SERVICE ENTRANCE: TYPE THHN/THWN-2, SINGLE CONDUCTORS IN RACEWAY.B.EXPOSED FEEDERS: TYPE THHN/THWN-2, SINGLE CONDUCTORS IN RACEWAY.C.FEEDERS CONCEALED IN CEILINGS, WALLS, PARTITIONS, AND CRAWLSPACES:.D.FEEDERS CONCEALED IN CONCRETE, BELOW SLABS-ON-GRADE, AND UNDERGROUND:TYPE THHN/THWN-2, SINGLE CONDUCTORS IN RACEWAY.E.EXPOSED BRANCH CIRCUITS, INCLUDING IN CRAWLSPACES: TYPE THHN/THWN-2,SINGLE CONDUCTORS IN RACEWAY.F.BRANCH CIRCUITS CONCEALED IN CEILINGS, WALLS, AND PARTITIONS: TYPETHHN/THWN-2, SINGLE CONDUCTORS IN RACEWAY.G.BRANCH CIRCUITS CONCEALED IN CONCRETE, BELOW SLABS-ON-GRADE, ANDUNDERGROUND: TYPE THHN/THWN-2, SINGLE CONDUCTORS IN RACEWAY.H.CORD DROPS AND PORTABLE APPLIANCE CONNECTIONS: TYPE SO, HARDSERVICE CORD WITH STAINLESS-STEEL, WIRE-MESH, STRAIN RELIEF DEVICE ATTERMINATIONS TO SUIT APPLICATION.1.4FIELD QUALITY CONTROLA.TESTING: BY CONTRACTOR.END OF SECTION 260519SECTION 260519 - LOW-VOLTAGE (600V OR LESS) ELECTRICAL POWER CONDUCTORS AND CABLESELECTRICALMETAL-CLAD CABLE.1.1QUALITY ASSURANCEA.QUALITY STANDARD FOR GROUNDING AND BONDING MATERIALS ANDEQUIPMENT: UL 467.1.2PRODUCTSA.INSULATED CONDUCTORS: COPPER WIRE OR CABLE.B.BARE COPPER CONDUCTORS:1.SOLID CONDUCTORS.2.STRANDED CONDUCTORS.3.TINNED CONDUCTORS.4.STRANDED BONDING CONDUCTORS.5.COPPER TAPE BRAIDED BONDING JUMPERS.6.TINNED-COPPER BRAIDED BONDING JUMPERS.C.CONNECTORS: BOLTED AND EXOTHERMIC-WELDED TYPE.D.GROUNDING ELECTRODES:1.GROUND RODS: COPPER-CLAD STEEL, SECTIONAL TYPE WITH GROUND WELLAND COVER.1.3FIELD QUALITY CONTROLA.GROUND RESISTANCE TESTING: BY CONTRACTOR-ENGAGED AGENCY.END OF SECTION 260526SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMSELECTRICAL1.1PERFORMANCE REQUIREMENTSA.DESIGN SUPPORTS FOR MULTIPLE RACEWAYS CAPABLE OF SUPPORTINGCOMBINEDWEIGHT OF SUPPORTED SYSTEMS AND ITS CONTENTS.B.DESIGN EQUIPMENT SUPPORTS CAPABLE OF SUPPORTING COMBINED OPERATINGWEIGHT OF SUPPORTED EQUIPMENT AND CONNECTED SYSTEMS ANDCOMPONENTS.1.2PRODUCTSA.SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS:1.STEEL SLOTTED SUPPORT SYSTEMS WITHMETALLICCOATINGS.2.NONMETALLIC SLOTTED SUPPORT SYSTEMS.3.RACEWAY AND CABLE SUPPORTS.4.STEEL AND MALLEABLE-IRON CONDUIT AND CABLE HANGERS, CLAMPS, ANDASSOCIATED ACCESSORIES.5.SUPPORT FOR NON-ARMORED CONDUCTORS AND CABLES IN VERTICALCONDUIT RISERS.6.STRUCTURAL STEEL FOR FABRICATED SUPPORTS AND RESTRAINTS.7.MOUNTING, ANCHORING, AND ATTACHMENT COMPONENTS:a.POWDER-ACTUATED FASTENERS.b.MECHANICAL-EXPANSION ANCHORS.c.CONCRETE INSERTS.d.CLAMPS FOR ATTACHMENT TO STEEL STRUCTURAL ELEMENTS.e.ALL STEEL, SPRINGHEAD TOGGLE BOLTS.f.THREADED HANGER RODS.B.FABRICATED METAL EQUIPMENT SUPPORT ASSEMBLIES: WELDED OR BOLTEDSTEEL SHAPES.END OF SECTION 260529SECTION 260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMSELECTRICALPART 1 - GENERAL1.1MATERIALSA.METAL CONDUITS, TUBING, AND FITTINGS:1.GRC.2.EMT.3.FMC: ZINC-COATED STEEL.4.LFMC.5.FITTINGS:a.EMT: STEEL, SETSCREW OR COMPRESSION TYPE.b.EXPANSION FITTINGS.B.NONMETALLIC CONDUITS, TUBING, AND FITTINGS:1.RNC.2.FITTINGS: MATCH CONDUIT.3.SOLVENT CEMENTS AND ADHESIVE PRIMERS SHALL HAVE A VOC CONTENT OF510 AND 550 G/L OR LESS, RESPECTIVELY.C.METAL WIREWAYS AND AUXILIARY GUTTERS: SHEET METAL WITHSCREW COVERS.D.SURFACE METAL RACEWAYS: METAL, GALVANIZED STEEL, WITH SNAP-ON COVERS.E.BOXES, ENCLOSURES, AND CABINETS:1.METAL OUTLET AND DEVICE BOXES:FERROUS ALLOY.2.METAL FLOOR BOXES: CAST METAL OR SHEET METAL, FULLYADJUSTABLE.3.LUMINAIRE OUTLET BOXES: NONADJUSTABLE, DESIGNED FOR ATTACHMENT OFLUMINAIRE WEIGHING 50 LB (23 KG).4.SMALL SHEET METAL PULL AND JUNCTION BOXES.5.CAST-METAL ACCESS, PULL, AND JUNCTION BOXES.6.BOX EXTENSIONS.7.GANGABLE BOXES ARE PROHIBITED.8.HINGED-COVER ENCLOSURES: METAL.9.CABINETS: GALVANIZED STEEL.F.HANDHOLES AND BOXES FOR EXTERIOR UNDERGROUND WIRING: POLYMERCONCRETE WITH POLYMER-CONCRETE FRAME AND COVER, PROTOTYPE TESTEDFOR COMPLIANCE WITH SCTE 77.1.CONFIGURATION:INTEGRAL CLOSED BOTTOM.2.WEATHERPROOF COVER.3.COVER LEGEND:"ELECTRIC.".1.2RACEWAY APPLICATIONA.OUTDOORS:1.EXPOSED: GRC.2.CONCEALED, ABOVEGROUND: RNC, TYPE EPC-40-PVC.3.UNDERGROUND: RNC, TYPE EPC-40-PVC, DIRECT BURIED.4.CONNECTION TO VIBRATING EQUIPMENT: LFMC.5.BOXES AND ENCLOSURES, ABOVEGROUND: TYPE 3R OR TYPE 4.B.INDOORS:1.EXPOSED, NOT SUBJECT TO PHYSICAL DAMAGE: GRC.2.EXPOSED, NOT SUBJECT TO SEVERE PHYSICAL DAMAGE: EMT.3.CONCEALED: EMT.4.CONNECTION TO VIBRATING EQUIPMENT: FMC, EXCEPT LFMC IN DAMP OR WETLOCATIONS.5.DAMP OR WET LOCATIONS: GRC.6.BOXES AND ENCLOSURES: TYPE 1, EXCEPT TYPE 4STAINLESS STEEL IN DAMP OR WET LOCATIONS.C.MINIMUM RACEWAY SIZE:3/4-INCH TRADE SIZE.D.RACEWAY FITTINGS: COMPATIBLE WITH RACEWAYS AND SUITABLE FOR USE ANDLOCATION.1.RIGID AND INTERMEDIATE STEEL CONDUIT: THREADED RIGID STEEL CONDUITFITTINGS.2.PVC EXTERNALLY COATED, RIGID STEEL CONDUITS: FITTINGS LISTED FORUSE WITH THIS TYPE OF CONDUIT.3.EMT:COMPRESSION FITTINGS.4.FLEXIBLE CONDUIT: FITTINGS LISTED FOR USE WITH FLEXIBLE CONDUIT.END OF SECTION 260533SECTION 260533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMSELECTRICAL1.1CABLE TRAY TYPESA.LADDER.B.SINGLE RAIL.C.TROUGH.1.2MATERIALSA.CABLE TRAYS, FITTINGS, AND ACCESSORIES: STEEL.1.FACTORY-STANDARD PRIMER; WITH CHROMIUM-ZINC-PLATED HARDWARE.2.MILL GALVANIZED BEFORE FABRICATION; WITH GALVANIZED HARDWARE.3.ELECTROGALVANIZED BEFORE FABRICATION; WITH GALVANIZED HARDWARE.4.HOT-DIP GALVANIZED AFTER FABRICATION; WITH CHROMIUM-ZINC-PLATED HARDWARE.5.POWDER-COAT ENAMEL PAINT; WITH CHROMIUM-ZINC-PLATED HARDWARE.6.BLACK OXIDE FINISH FOR SUPPORT ACCESSORIES AND MISCELLANEOUSHARDWARE.7.BLACK.B.CABLE TRAYS, FITTINGS, AND ACCESSORIES: ALUMINUM; WITH STAINLESS-STEELHARDWARE.C.CABLE TRAY ACCESSORIES:1.COVERS:LOUVERED TYPE.2.BARRIER STRIPS.3.CABLE TRAY SUPPORTS AND CONNECTORS.D.WARNING SIGNS: 1-1/2-INCH- (40-MM-) HIGH, BLACK LETTERS ON YELLOWBACKGROUND WITH LEGEND "WARNING! NOT TO BE USED AS WALKWAY, LADDER, ORSUPPORT FOR LADDERS OR PERSONNEL".1.3SOURCE QUALITY CONTROLA.TESTED ACCORDING TO NEMA FG 1.END OF SECTION 260536SECTION 260536 - CABLE TRAYS FOR ELECTRICAL SYSTEMSELECTRICAL1.1MATERIALSA.SLEEVES:1.SCHEDULE 40 STEEL PIPE.2.CAST-IRON PIPE.3.GALVANIZED-STEEL SHEET FOR CONDUITS PENETRATING NON-FIRE-RATEDGYPSUM-BOARD ASSEMBLIES.4.MOLDED-PE OR -PP PIPE.5.GALVANIZED-STEEL SHEET FOR RECTANGULAR OPENINGS.B.SLEEVE-SEALS:1.EPDM RUBBER SEALING ELEMENTS.2.CARBON-STEEL PRESSURE PLATES.3.CARBON-STEEL, WITH CORROSION-RESISTANT COATING, CONNECTING BOLTS AND NUTS.C.HYDRAULIC-CEMENT GROUT.D.SILICONE SEALANTS:1.SINGLE-COMPONENT, SILICONE-BASED, NEUTRAL-CURING ELASTOMERICSEALANT.2.MULTICOMPONENT, SILICONE-BASED LIQUID ELASTOMERIC NONSHRINKINGFOAM.3.VOC CONTENT OF 250 G/L OR LESS.END OF SECTION 260544SECTION 260544 - SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLINGELECTRICAL1.1QUALITY ASSURANCEA.COMPLY WITH ANSI A13.1 AND IEEE C2.1.2PRODUCTSA.POWER AND CONTROL RACEWAY IDENTIFICATION:VINYL LABELSB.POWER AND CONTROL CABLE IDENTIFICATION:VINYL LABELSC.CONDUCTOR IDENTIFICATION:SNAP-AROUND LABELS.D.FLOOR MARKING TAPE: 2-INCH- (50-MM-) WIDE PRESSURE-SENSITIVE VINYL TAPE.E.UNDERGROUND-LINE WARNING TAPE:PIGMENTED POLYOLEFINF.WARNING LABELS AND SIGNS:SELF-ADHESIVE WARNING LABELS.G.INSTRUCTION SIGNS:ENGRAVED.H.EQUIPMENT IDENTIFICATION LABELS:ENGRAVED, LAMINATEDACRYLIC OR MELAMINE PLASTIC.END OF SECTION 260553SECTION 260553 - IDENTIFICATION FOR ELECTRICAL SYSTEMSELECTRICAL1.1PRODUCTSA.TIME SWITCHES:ELECTRONIC, PROGRAMMABLE UNITS, WITH SINGLE CHANNEL;ASTRONOMIC TIME, SEVEN-DAYPROGRAMMABLE WITH MINIMUM 8 ON/OFF SET POINTS PER 24 HOURSCHEDULE.B.OUTDOOR PHOTOELECTRIC SWITCHES: SOLID STATE, WITH DRY CONTACTS,15-SECOND TIME DELAY, AND METAL-OXIDE VARISTOR SURGE PROTECTION.C.DAYLIGHT-HARVESTING SWITCHING CONTROLS: CEILING MOUNTED WITHADJUSTABLE TIME DELAY AND SET-POINTS.D.INDOOR OCCUPANCY SENSORS:DUAL-TECHNOLOGY TYPE,WITH SEPARATE, EXTERNALLY MOUNTED RELAY UNIT.E.SWITCHBOX-MOUNTED OCCUPANCY SENSORS.F.LIGHTING CONTACTORS: ELECTRICALLY OPERATED ANDELECTRICALLY HELD, WITH NONFUSED DISCONNECT INNEMA 250 ENCLOSURE. PROVIDE WITH CONTROL AND PILOT DEVICES ASINDICATED IN PLANS.G.EMERGENCY SHUNT RELAY: NORMALLY CLOSED, ELECTRICALLY HELD,ARRANGED FOR WIRING IN PARALLEL WITH AUTOMATIC SWITCHING CONTACTS.H.CONTROL CABLES:1.POWER CABLES: NOT SMALLER THAN NO. 12 AWG.2.CLASSES 2 AND 3 CONTROL CABLES: STRANDED-COPPER CONDUCTORS, NOTSMALLER THAN NO. 18 AWG.3.CLASS 1 CONTROL CABLES: STRANDED-COPPER CONDUCTORS, NOT SMALLERTHAN NO. 14 AWG.END OF SECTION 260923SECTION 260923 - LIGHTING CONTROL DEVICESELECTRICAL1.1QUALITY ASSURANCEA.MANUFACTURER QUALIFICATIONS: ISO 9001 OR 9002 CERTIFIED.1.2PRODUCTSA.GENERAL REQUIREMENTS FOR PANELBOARDS:1.CONSTRUCTED TO WITHSTAND SEISMIC FORCES.2.ENCLOSURES:SURFACE MOUNTED.a.FRONT: HINGED COVER WITH KEY LOCK.b.OPTIONAL ENCLOSURE FEATURES:SKIRT FOR SURFACE-MOUNTEDPANELBOARDS.c.DIRECTORY CARD.3.INCOMING MAINS:CONVERTIBLE BETWEEN TOP AND BOTTOM4.PHASE, NEUTRAL AND GROUND BUSES: TIN-PLATED COPPER.5.CONDUCTOR CONNECTORS:a.MATERIAL: TIN-PLATED COPPER.b.MAIN AND NEUTRAL LUGS: MECHANICAL TYPE.c.FEED-THROUGH LUGS: MECHANICAL TYPE.6.PERCENTAGE OF FUTURE SPACE CAPACITY:FIFTEENPERCENT.7.SERVICE EQUIPMENT LABEL FOR PANELBOARDS INCORPORATING ONE OR MOREMAIN SERVICE DISCONNECTING AND OVERCURRENT PROTECTIVE DEVICES.B.PANELBOARD OR LOAD CENTER SHORT-CIRCUIT CURRENT RATING: FULLY RATEDTO INTERRUPT SYMMETRICAL SHORT-CIRCUIT CURRENT AVAILABLE AT TERMINALS.LISTEDSERIES RATED SYSTEM MAY BE USED IF APPROVED BY EOR TO LIMIT FAULTTO BELOW 22K AIC FOR GFI BREAKERS.1.MAINS: LUGS ONLY.2.BRANCH OVERCURRENT PROTECTIVE DEVICES FOR CIRCUIT-BREAKER FRAMESIZES LARGER THAN 125 A: BOLT-ON CIRCUIT BREAKERS.C.LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARDS:1.MAINS: LUGS ONLY.2.BRANCH OVERCURRENT PROTECTIVE DEVICES: PLUG-IN CIRCUIT-BREAKERTYPE.3.DOORS: CONCEALED HINGE.D.LOAD CENTERS:1.MAINS: LUGS ONLY.2.BRANCH CIRCUIT BREAKERS: PLUG-IN.3.DOORS: CONCEALED HINGE.4.CONDUCTOR CONNECTORS: MECHANICAL TYPE.E.DISCONNECTING AND OVERCURRENT PROTECTIVE DEVICES:1.CIRCUIT BREAKERS:THERMAL-MAGNETIC TYPES.2.GFI CIRCUIT BREAKERS: RATED FOR PERSONNEL.3.AFCI CIRCUIT BREAKERS: AS REQUIRED BY CODE.4.OPTIONS AND TYPES AS NEEDED.F.IDENTIFICATION:1.PANELBOARD LABELS: MANUFACTURER'S NAME AND TRADEMARK, VOLTAGE,AMPERAGE, NUMBER OF PHASES, ARC FLASH HAZARD, AND NUMBER OF POLESSHALL BE LOCATED ON THE INTERIOR OF THE PANELBOARD DOOR.2.BREAKER LABELS: FACEPLATE SHALL LIST CURRENT RATING, UL AND IECCERTIFICATION STANDARDS, AND AIC RATING.3.CIRCUIT DIRECTORY: DIRECTORY CARD INSIDE PANELBOARD DOOR, MOUNTEDINMETAL FRAME WITH TRANSPARENT PROTECTIVE COVER.G.ACCESSORIES:1.ACCESSORY SET INCLUDING TOOLS.2.PORTABLE TEST SET: FOR TESTING FUNCTIONS OF SOLID-STATE TRIP DEVICESWITHOUT REMOVING FROM PANELBOARD.1.3FIELD QUALITY CONTROLA.TESTING: BY CONTRACTOR.END OF SECTION 262416SECTION 262416 - PANELBOARDSELECTRICAL1.1EQUIPMENT FOR ELECTRICITY METERING BY UTILITY COMPANYA.UTILITY-COMPANY-COMPLIANT CURRENT-TRANSFORMER CABINETS: COMPLY WITHREQUIREMENTS OF ELECTRICAL-POWER UTILITY COMPANY.B.METER SOCKETS: COMPLY WITH REQUIREMENTS OF ELECTRICAL-POWER UTILITYCOMPANY.END OF SECTION 262713SECTION 262713 - ELECTRICITY METERINGELECTRICAL1.1PRODUCTSA.RECEPTACLES: DUPLEX, 125 V, 20 A.1.STRAIGHT BLADE: CONVENIENCE AND ISOLATED GROUND.2.GFCI: FEED THROUGH.3.TWIST-LOCKING TYPE WITH ISOLATED-GROUND TERMINAL.B.PENDANT CORD-CONNECTOR DEVICES WITH EXTERNAL CABLE GRIP.C.CORD AND PLUG SETS: MATCH VOLTAGE AND CURRENT RATINGS AND NUMBER OFCONDUCTORS TO REQUIREMENTS OF EQUIPMENT BEING CONNECTED.D.TOGGLE SWITCHES: 120/277 V, 20 A.1.PILOT-LIGHT SWITCHES.2.KEY-OPERATED SWITCHES.E.WALL-BOX DIMMERS:1.MODULAR, FULL-WAVE, SOLID-STATE UNITS WITH SLIDER CONTROL.a.INCANDESCENT: SOFT TAP OR OTHER QUIET SWITCH; EMI/RFIFILTER TO ELIMINATE INTERFERENCE.b.FLUORESCENT: TRIM POTENTIOMETER FOR LOW-END DIMMING.c.LED: COMPATIBLE WITH LED DRIVER OR LAMP.F.WALL PLATES:1.MATERIAL FOR WORKROOM:SATIN-FINISHED STAINLESS STEEL.2.MATERIAL FOR BAR:SATIN-FINISHED STAINLESS STEEL.3.MATERIAL FOR CUSTOMER AREAS:THERMOPLASTIC WITH COLOR OPTION PERSTARBUCKS.G.FLOOR SERVICE FITTINGS: MODULAR, (DUAL SERVICE IF NEEDED), WITH POWERRECEPTACLE (AND VOICE AND DATA COMMUNICATION OUTLET IF NEEDED).1.TYPE:FLUSH2.SERVICE PLATE:RECTANGULAR.3.VOICE AND DATA COMMUNICATION OUTLET:BLANK COVER WITH BUSHED CABLEOPENING.H.POKE-THROUGH ASSEMBLIES: BELOW-FLOOR JUNCTION BOX WITH MULTICHANNELED,THROUGH-FLOOR RACEWAY/FIRESTOP AND DETACHABLE FLOOR SERVICE-OUTLETASSEMBLY.1.SERVICE-OUTLET ASSEMBLY: SURFACE TYPE.2.SIZE:4 INCHES (100 MM).I.MULTIOUTLET ASSEMBLIES: MANUFACTURED AND LISTED METAL RACEWAYS.J.SERVICE POLES: TO EXTEND POWER AND VOICE AND DATA COMMUNICATIONWIRING FROM DISTRIBUTION WIRING IN CEILING TO DEVICES OR OUTLETS IN POLENEAR FLOOR.1.FINISH:PAINTED.2.POWER RECEPTACLES: TWO, DUPLEX, 20 A.3.VOICE AND DATA COMMUNICATION OUTLETS:BLANK INSERTK.FINISHES:1.CONNECTED TO NORMAL POWER SYSTEM:WHITE2.CONNECTED TO EMERGENCY POWER SYSTEM:RED3.ISOLATED-GROUND RECEPTACLES:AS SPECIFIED ABOVE, WITHORANGE TRIANGLE ON FACE.END OF SECTION 262726SECTION 262726 - WIRING DEVICESELECTRICAL1.1PRODUCTSA.FUSIBLE SWITCHES:1.GENERAL DUTY, SINGLE THROW, [240-V] [600V] AC, 800 A AND SMALLER: UL 98ANDNEMA KS 1, NEMA 3R TYPE GD.2.ACCESSORIES:a.EQUIPMENT GROUND KIT.b.NEUTRAL KIT.c.ISOLATED GROUND KIT.d.CLASS R FUSE KIT.e.AUXILIARY CONTACT KIT.f.HOOKSTICK HANDLE.g.LUGS: MECHANICAL.h.SERVICE-RATED SWITCHES.i.ACCESSORY CONTROL POWER.B.NONFUSIBLE SWITCHES:1.GENERAL DUTY, SINGLE THROW, [240-V] [600V] AC, 600 A AND SMALLER: UL 98ANDNEMA KS 1, NEMA 3R TYPE GD.2.ACCESSORIES:a.EQUIPMENT GROUND KIT.b.NEUTRAL KIT.c.ISOLATED GROUND KIT.c.AUXILIARY CONTACT KIT.e.HOOKSTICK HANDLE.f.LUGS: MECHANICAL.g.ACCESSORY CONTROL POWER.C.MOLDED-CASE CIRCUIT BREAKERS:1.THERMAL-MAGNETIC TYPE.2.ADJUSTABLE INSTANTANEOUS-TRIP TYPE.3.ELECTRONIC-TRIP TYPE.4.CURRENT-LIMITING TYPE.5.INTEGRALLY FUSED TYPE.6.GFCI TYPE.7.GFEP TYPE.8.FEATURES AND ACCESSORIES:a.LUGS: MECHANICAL.b.TYPE SWD FOR SWITCHING FLUORESCENT LIGHTING LOADS.c.TYPE HID FOR FEEDING FLUORESCENT AND HIGH-INTENSITY DISCHARGELIGHTING CIRCUITS.d.GROUND-FAULT PROTECTION:INTEGRALLY MOUNTED, SELF-POWERED TYPE.e.SHUNT TRIP.f.UNDERVOLTAGE TRIP: 35 TO 75 PERCENT OF RATED VOLTAGE WITHOUTINTENTIONAL TIME DELAY.g.AUXILIARY CONTACTS:TWO SPDT SWITCHES.h.ALARM SWITCH: ONENO CONTACT.i.KEY INTERLOCK KIT.j.ZONE-SELECTIVE INTERLOCKING: INTEGRAL WITHELECTRONIC TRIP.k.ELECTRICAL OPERATOR.l.ACCESSORY CONTROL POWER.D.MOLDED-CASE SWITCHES:1.MCCB WITH FIXED, HIGH-SET INSTANTANEOUS TRIP ONLY, AND SHORT-CIRCUITWITHSTAND RATING EQUAL TO EQUIVALENT BREAKER FRAME SIZEINTERRUPTING RATING.2.FEATURES AND ACCESSORIES:a.LUGS: MECHANICAL.b.GROUND-FAULT PROTECTION: REMOTE-MOUNTED AND POWERED TYPE.c.SHUNT TRIP.d.UNDERVOLTAGE TRIP: 35 TO 75 PERCENT OF RATED VOLTAGE WITHOUTINTENTIONAL TIME DELAY.e.AUXILIARY CONTACTS:TWO SPDT SWITCHESf.ALARM SWITCH: ONENO CONTACT.g.KEY INTERLOCK KIT.h.ZONE-SELECTIVE INTERLOCKING: INTEGRAL WITH REMOTE GROUND-FAULTTRIP UNIT.i.ELECTRICAL OPERATOR.j.ACCESSORY CONTROL POWER.E.ENCLOSURES:1.INDOOR, DRY AND CLEAN LOCATIONS: NEMA 250, TYPE 1.2.OUTDOOR LOCATIONS: NEMA 250, TYPE 3R.1.2FIELD QUALITY CONTROLA.TESTING: BY CONTRACTOR.1.3ADJUSTINGA.SET FIELD-ADJUSTABLE CIRCUIT-BREAKER TRIP RANGES.END OF SECTION 262816SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERSELECTRICALSHEET NUMBER:SHEET TITLE:SCALE:STORE #:PROJECT #:PROJECT NAME: <br />PROJECT ADDRESS:C 2020 STARBUCKS COFFEE COMPANYRISSUE DATE:2401 UTAH AVENUE SOUTHSEATTLE, WASHINGTON 98134(206) 318-1575THESE DRAWINGS AND THE PROJECT MANUALARE CONFIDENTIAL AND SHALL REMAIN THESOLE PROPERTY OF STARBUCKSCORPORATION, WHICH IS THE OWNER OF THECOPYRIGHT IN THIS WORK. THEY SHALL NOTBE REPRODUCED (IN WHOLE OR IN PART),SHARED WITH THIRD PARTIES OR USED IN ANYMANNER ON OTHER PROJECTS OREXTENSIONS TO THIS PROJECT WITHOUT THEPRIOR WRITTEN CONSENT OF STARBUCKSCORPORATION. THESE DRAWINGS ANDSPECIFICATIONS ARE INTENDED TO EXPRESSDESIGN INTENT FOR A PROTOTYPICALSTARBUCKS STORE (WHICH IS SUBJECT TOCHANGE AT ANYTIME) AND DO NOT REFLECTACTUAL SITE CONDITIONS. NEITHER PARTYSHALL HAVE ANY OBLIGATION NOR LIABILITY TOTHE OTHER (EXCEPT STATED ABOVE) UNTIL AWRITTEN AGREEMENT IS FULLY EXECUTED BYBOTH PARTIES.STARBUCKS TEMPLATE VERSION: i2020.10.23STARBUCKSRSR. DESIGN MANAGER:DESIGN MANAGER:CHECKED BY:Revision ScheduleRevDateByDescription01/28/21ACIESFINAL REVIEW SET400 N McCarthy Blvd.Copyright c 2021info@acies.netfx: (408) 522-5260ph: (408) 522-5255Suite 250, Milpitas, CA 95035ENGINEERINGHIGHWAY 99 & WATERLOO <br />4426 EAST WATERLOO ROAD <br />STOCKTON, CA 95215 <br />COUNTY OF SAN JOAQUIN23871-06801-28-217957JESSICA RAMOS02/05/21ACIESPERMIT SETTGHTE-002ELECTRICAL OUTLINESPECIFICATIONS