Laserfiche WebLink
WET -PIPE SPRINKLER SYSTEMS <br />Section 15360 <br />15-1207 <br />soffits shall be of manufactures standards as selected by the architect. <br />C. Spare Sprinkler Heads: Furnish spare sprinkler heads placed in an emergency <br />cabinet. For each cabinet provide one sprinkler wrench. The cabinet will be of <br />No. 20 gauge pressure steel with red lacquer finish complete with manufacturer <br />standard labeling. The spare heads shall be representative of, and in proportion <br />to, the number of each type and temperature of heads installed. Locate cabinet <br />where shown on plans or as directed by owner. <br />2.02 PIPE AND FITTINGS <br />A. Pipe fittings for installation below ground shall be cement lined, cast iron <br />conforming to the requirements of American Water Works Association Standard <br />Specification for cast iron special castings, Class D, 150 Ib., AWWA C151 <br />mechanical or push -on joint; with AWWA C104 cement -mortar lining, "Blue Brut" <br />or PVC pressure pipe AMA C900, UL approved for fire line service. If PVC <br />premastering pipe is used with mechanical joint fittings, install according to <br />manufacturer's requirements and recommendations. <br />B. Fire sprinkler piping, from base of riser to 5-0" outside building (Below ground): <br />C. Pipe: Acceptable piping materials are Class 50 cement -lined ductile iron with a <br />working pressure of 250 psi per NFPA 24. All piping shall be listed for fire <br />protection service. <br />D. Fittings: Fittings shall be rated to a minimum of 250 psi and meet applicable <br />requirements of ANSI/AWWA and NFPA 24. <br />E. All materials shall comply with NFPA / ANSI & AWWA <br />F. The flange and spigot piece at the base of the riser shall be secured to the <br />underground elbow at the base of the riser with two %" stainless steel tie rods for <br />6" riser (for underground supply piping). <br />G. Pipe for installation above ground shall conform to ASTM A 795, A 53, or A135. <br />Thin wall pipe with grooved fittings and couplings may be used for pipe 2" and <br />larger. Piping for sizes 1'/2' and smaller shall be Schedule 40 pipe with welded, <br />grooved or screwed fittings. No thin wall pipe shall be used in conjunction with <br />screwed fittings. <br />H. Gate valves shall be approved rising stem type (OS&Y). All shut off valves shall <br />be equipped with tamper switches. <br />I. All exposed valves shall be chained to prevent accidental shutting of the valves. <br />J. Fire sprinkler riser shall comply with all applicable codes. Supports, Anchors, <br />Bracing — See All Sections 21 05 29 and 21 05 48. <br />K. Piping Penetration Auxiliaries: Conform to NFPA 13 and the following: <br />3 <br />