DUCTLESS SPLIT SYSTEM AC UNITS <br />Section 15865 <br />15-1207 <br />F. Indoor Unit Coil: <br />1. The evaporator coil shall be of nonferrous construction with pre -coated aluminum <br />strake fins on copper tubing. The multi -angled heat exchanger shall have a <br />modified fin shape that reduces air resistance for a smoother, quieter airflow. All <br />tube joints shall be brazed with PhosCopper or silver alloy. The coils shall be <br />pressure tested at the factory. A condensate pan and drain shall be provided <br />under the coil. <br />G. Indoor Unit Electrical: <br />1. The electrical power of the unit shall be 208 volts or 230 volts, 1 phase, 60 hertz. <br />a. The system shall be capable of satisfactory operation within voltage limits <br />of 198 volts to 253 volts. <br />2. The power to the indoor unit shall have an option of being supplied from the <br />outdoor unit, using Mitsubishi Electric A -Control system or separate power <br />source for indoor and outdoor units. <br />H. Unit Control: <br />The control system shall consist of two (2) microprocessors, one on each indoor <br />and outdoor unit, interconnected by a single non -polar two -wire cable. <br />2. Field wiring shall run directly from the indoor unit to the wall mounted controller <br />with no splices. <br />a. For A -Control, a three (3) conductor 14 ga. AWG wire with ground shall <br />provide power feed and bi-directional control transmission between the <br />outdoor and indoor units. <br />b. Where separate power is supplied to the indoor and outdoor units, a two <br />(2) 20 ga. AWG wire shall be run between the units to provide forbid - <br />directional control communication. <br />3. The system shall be capable of automatic restart when power is restored after <br />power interruption. The system shall have self -diagnostics ability, including total <br />hours of compressor run time. Diagnostics codes for indoor and outdoor units <br />shall be displayed on the wired controller panel. <br />4. The microprocessor located in the indoor unit shall have the capability of <br />monitoring return air temperature and indoor coil temperature, receiving and <br />processing commands from the wired controller, providing emergency operation <br />and controlling the outdoor unit. <br />5. The indoor unit shall be connected to a wall mounted wired controller to perform <br />input functions necessary to operate the system. <br />a. The wired controller shall have a large multi -language DOT liquid crystal <br />display (LCD) presenting contents in eight (8) different languages, including <br />English, French, Chinese, German, Japanese, Spanish, Russian, and <br />Italian. <br />b. There shall be a built-in weekly timer with up to eight pattern settings per <br />day. <br />C. The controller shall consist of an On/Off button, Increase/Decrease Set <br />Temperature buttons, a Cool/Dry/Fan mode selector, a Timer Menu button, <br />4 <br />