Laserfiche WebLink
DUCTLESS SPLIT SYSTEM AC UNITS <br />Section 15865 <br />15-1207 <br />J. Outdoor Unit Cabinet: <br />1. The casing shall be constructed from galvanized steel plate, coated with a <br />finished with an electrostatically applied, thermally fused acrylic or polyester <br />powder coating for corrosion protection and have a munsell 3Y 7.8/1.1 finish. <br />2. The fan grille shall be of ABS plastic. <br />K. Outdoor Unit Fan: <br />1. Unit to be furnished with an AC fan motor. The fan motor shall be of aerodynamic <br />design for quiet operation, and the fan motor bearings shall be permanently <br />lubricated. The outdoor unit shall have horizontal discharge airflow. The fan <br />shall be mounted in front of the coil, pulling air across it from the rear and <br />dispelling it through the front. The fan shall be provided with a raised guard to <br />prevent contact with moving parts. <br />L. Outdoor Unit Coil: <br />1. The L shaped condenser coil shall be of copper tubing with flat aluminum fins to <br />reduce debris build up. <br />2. The coil shall be protected with an integral metal guard. <br />3. Refrigerant flow from the condenser shall be controlled by means of linear <br />expansion valve (LEV) metering orifice. The LEV shall be control by a <br />microprocessor controlled step motor. <br />M. Outdoor Unit Compressor: <br />1. The compressor shall be a DC rotary compressor with Variable Compressor <br />Speed Inverter Technology. <br />2. The compressor shall be driven by inverter circuit to control compressor speed. <br />3. The compressor speed shall dynamically vary to match the room load for <br />significantly increasing the efficiency of the system which results in vast energy <br />savings. <br />4. To prevent liquid from accumulating in the compressor during the off cycle, a <br />minimal amount of current shall be intermittently applied to the compressor motor <br />to maintain enough heat. <br />5. The outdoor unit shall have an accumulator and high pressure safety switch. <br />6. The compressor shall be mounted to avoid the transmission of vibration. <br />N. Outdoor Unit Electrical: <br />The electrical power of the unit shall be 208volts or 230 volts, 1 phase, 60 hertz. <br />a. The unit shall be capable of satisfactory operation within voltage limits of <br />198 volts to 253 volts. <br />2. The outdoor unit shall be controlled by the microprocessor located in the indoor <br />unit. <br />3. The control signal between the indoor unit and the outdoor unit shall be pulse <br />signal 24 volts DC. The unit shall have Pulse Amplitude Modulation circuit to <br />utilize 98% of input power supply. <br />0 <br />