EXHAUST FANS AND HOODS <br />Section 15880 <br />15-1207 <br />PART 1 — GENERAL <br />1.01 SUMMARY <br />A. This section includes exhaust systems including: <br />1. Roof Exhaust Fans <br />2. Roof Mounted Air Intake/Relief Hoods <br />3. Roof Curbs <br />B. For additional requirements, reference Section 01810 — Systems Commissioning. <br />1.02 REFERENCES <br />A. AFBMA 9 — Load Ratings and Fatigue Life for Ball Bearings. <br />B. AFBMA 11 — Load Ratings and Fatigue Life for Roller Bearings. <br />C. AMCA 99 — Standards Handbook <br />D. ACMA 210 — Laboratory Methods of Testing Fans for Rating Purposes <br />E. ACMA 300 — Test Code for Sound Rating Air Moving Devices <br />F. AMCA 301 — Method of Calculating Fan Sound Ratings form Laboratory Test Data <br />G. ANSI B3.15 <br />H. California Electrical Code (C.E.C.) <br />I. SMACNA — HVAC Duct Construction Standards <br />1.03 QUALITY ASSURANCE <br />A. Conform to AMCA bulletins regarding construction and testing. Fans shall bear AMCA <br />certified rating seal. <br />B. Fans of similar type shall be by the same manufacturer. <br />1.04 SUBMITTALS <br />A. Product Data: Submit complete data of materials proposed including the following: <br />1. Manufacturer. <br />2. Model. <br />3. Fan Type <br />4. Wheel type <br />5. Fan Construction Class <br />6. Fan size and arrangement <br />7. Dimensional data including bolt hole locations <br />8. Fan Weight <br />E <br />