Laserfiche WebLink
IDENTIFICATION FOR <br />ELECTRICAL SYSTEMS <br />Section 16010 <br />15-1207 <br />6) Examples: <br />Panels:2EH1 <br />225A <br />277/480V, 3PH, 4W <br />Served From: 2EHD1 <br />Transformers: ETX-1 <br />150KVA <br />480V - 120/208V, 3PH, 4W <br />Served From: EHD1 <br />Load Served: EL1 <br />Motor Control Centers: <br />Main Nameplate: <br />Each Compartment <br />MCC-NH1 <br />600A Main Bus <br />480V,3PH,3W <br />Served From:HDD1A-2 <br />EF -1 <br />20 HP <br />Switch Size: 100A <br />Starter Size: 1 <br />Disconnects or Individual Motor Starters. <br />EF -1 <br />20HP <br />480V,3PH,3W <br />Served From: MCCNH-1 <br />Signal: STB -3 <br />Public Address System <br />Served From: STBM <br />Nameplates for power system distribution equipment and devices are to be <br />colored as follows: (Unless otherwise noted) <br />1. 277/480 VAC Normal - Yellow with black letters <br />2. 120/208 VAC Normal - Blue with white letters <br />D. Nameplates for signal systems equipment and devices are to be black except as <br />follows: <br />1. Fire alarm and life safety - White with red letters <br />2. Security/Card access/CCTV systems - Green with white letters <br />3. Clock, intercom, sound, MATV, CATV: Magenta with white letters <br />4. Building management system (BMS): White with black letters <br />E. Label Installation: <br />S 1... 1_11 1� 11 I 1 L /• <br />1. instar label parallel to equipment lines. <br />4 <br />