Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8 . SUMP/ UDC TEST <br /> Test Method Developed by 0 Manufacturer ❑ Industry Standard Professional Engineer <br /> Test Type ❑ Pressure © Vacuum ❑x Hydrostatic <br /> Test Equipment Used : Caldwell Sump Tester <br /> Sump/ UDC ID Main Diesel STP Main Diesel Fill Reserve Diesel STP Reserve Diesel Fill <br /> Sump Manufacturer Fiberglass Fiberglass Fiberglass Fiberglass <br /> Sump Depth ( inches ) 79 84 ° 79° 81 " <br /> Sump Bottom to Top of 14" 15" <br /> Highest Pipe Penetration <br /> ( inches ) <br /> Test Start Time 9 : 15 am 9 : 15 am 10 : 00 am 10 : 00 am <br /> Initial Reading 1st Line 1st Line 1st Line 1st Line <br /> Test End Time 9 : 45 am 9 :45 am 10 : 30 am 10 : 30 am <br /> Final Reading 1st Line 1st Line 1st Line 1st Line <br /> Change in Reading 0 0 0 0 <br /> Pass/ Fail Criteria Pass Pass Pass Pass <br /> Tightness Test Results ❑x Pass ® Fail ❑x Pass 0 Fail ❑x Pass [r] Fail ❑x Pass © Fail <br /> Sump/ UDC ID New Oil STP New Oil Fill W/O Pipe Sump W/O Fill Sump <br /> Sump Manufacturer Fiberglass Fiberglass Fiberglass Fiberglass <br /> Sump Depth ( inches ) 80 " 82 " 42 " 48" <br /> Sump Bottom to Top of 13" 13" <br /> Highest Pipe Penetration <br /> ( inches ) <br /> Test Start Time 11 : 00 am 11 :45 am 11 :45 am <br /> Initial Reading 1st Line 1st Line 1st Line <br /> Test End Time 11 : 30 am 12 : 15 pm 12 : 15 pm <br /> Final Reading 1st Line 1st Line 1st Line <br /> Change in Reading 0 0 0 <br /> Pass/ Fail Criteria Pass Pass Pass <br /> Tightness Test Results ❑—I Pass Fail ❑x Pass ® Fail ❑x Pass ® Fail ❑x Pass L' Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail' and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section . <br /> Page 3 of 5 <br />