Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by ❑ Manufacturer El Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br /> Test Equipment Used: Incon Tester <br /> Sump/UDC ID UDC 1/2 UDC 3/4 UDC 5/6 UDC 7/8 <br /> Sump Manufacturer Bravo Bravo Bravo Bravo <br /> Sump Depth (inches) 12" 12" 12" 12" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 4" 4" 4" 4" <br /> (inches) <br /> Test Start Time 11:26 am 11:26 am 11:26 am 11:26 am <br /> Initial Reading 1.7422 1.4320 2.1439 1.2938 <br /> Test End Time 11:41 am 11:41 am 11:41 am 11:41 am <br /> Final Reading 1.7420 1.4322 2.1346 1.2759 <br /> Change in Reading 0.0002 0.0002 0.0093 0.0179 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results 0 Pass ❑ Fail 0 Pass ❑ Fail ❑ Pass 0 Fail ❑ Pass 0 Fail <br /> Sump/UDC ID UDC 9/10 UDC 11/12 <br /> Sump Manufacturer Bravo Bravo <br /> Sump Depth (inches) 12" 12" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 4" 4" <br /> (inches) <br /> Test Start Time 12:23 pm 12:23 pm <br /> Initial Reading 0.8039 2.2976 <br /> Test End Time 12:38 pm 12:38 pm <br /> Final Reading 0.8036 2.2973 <br /> Change in Reading 0.0003 0.0003 <br /> Pass/Fail Criteria 0.002 0.002 <br /> Tightness Test Results 0 Pass ❑ Fail 0 Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />