Laserfiche WebLink
S A N J 0 A Q I I I Irl Environmental Health Department <br /> CCUN r <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> COUNTRY CLUB MOBIL CIRCLE K 2575 COUNTRY CLUB BLVD, STOCKTON January 18, 2023 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 301 HSC 25292.1(a)Failure to operate UST system to prevent unauthorized releases including leaks, spills and overfills. <br /> OBSERVATION: The smart sensors, S1 87 product, S3 91 product, S5 diesel product,were in alarm since January <br /> 2022. <br /> REGULATION GUIDANCE: The continuous monitoring system shall be maintained to detect the entry of the liquid <br /> or vapor phase of the hazardous substance stored in the primary containment into the secondary containment, and <br /> to detect water intrusion into the secondary containment. <br /> CORRECTIVE ACTION: Correct immediately by having a properly licensed,trained, and certified contractor replace <br /> the failed component with a functional component(LG 113-x listed, if applicable), and obtain a permit within one <br /> business day from the EHD, if needed. If the failed component can't be replaced immediately,there is a possibility <br /> that the 87,91, and diesel UST system may be red tagged to prevent fuel inputs. <br /> This is a Class II violation. <br /> 302 CCR 2630(d), 2641(a)Leak detection equipment not installed/maintained/located to detect leaks at earliest <br /> opportunity. <br /> 1)OBSERVATION: <br /> -The VR 208 sensor in UDC 3/4 was raised approximately 4 inches off the lowest point of the sump and not located <br /> to detect a leak at the earliest opportunity. <br /> -The VR 208 sensor in UDC 7/8 was raised approximately 1 inch off the lowest point of the sump and not located to <br /> detect a leak at the earliest opportunity. <br /> REGULATION GUIDANCE: Monitoring equipment shall be maintained to be able to detect a leak at the earliest <br /> possible opportunity. <br /> CORRECTIVE ACTION: The sensor was relocated to the lowest point of the sump by the service technician. <br /> Ensure that all monitoring equipment is maintained and located to detect a leak at the earliest opportunity. <br /> ------------------------------------------------------------------------------------ <br /> 2)OBSERVATION:The smart sensors were found to be in alarm since[DATE]and actions have not been taken to <br /> address the alarm. <br /> REGULATION GUIDANCE:All monitoring equipment shall be maintained to be able to detect a leak at the earliest <br /> possible opportunity. <br /> CORRECTIVE ACTION: Immediately contact a properly licensed,trained, and certified contractor to address the <br /> alarm under permit and inspection of the EHD. <br /> This is a Class II violation. <br /> FA0006439 PR0231070 SCO01 01/18/2023 <br /> EHD 23-01 Rev.12/06/2021 Page 8 of 10 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />